Check Gas Pressure; Manual Control; Millivolt Control - Vermont Castings PH24 Appliance Installation And Operating Instructions

Unvented gas log heater/ vented decorative
Table of Contents

Advertisement

INSTALLATION

CHECK GAS PRESSURE

The heater gas inlet connection is a 3/8" NPT at the valve.
All units have the inlet connection on the right side, when
you face the unit. To connect from the opposite side, route
the pipe under the rear portion of the unit.
When tightening up the joint to the valve, hold the valve
securely to prevent movement.
Test all gas joints from the gas meter to the heater valve
for leaks using a gas analyzer or soap and water solution
after completing connection. DO NOT USE AN OPEN
FLAME.
Check the gas pressure with the appliance burning and
the control set to HIGH.

MANUAL CONTROL

Figure 13
The pressure regulator is preset and locked to dis-
courage tampering. If the pressure is not as specifi ed,
replace the regulator with the correct part from the parts
list in this manual.
Remove 1/8" NPT plug, located on side of regulator body.
Install fi tting and tubing to pressure gauge. After taking
pressure reading, reinstall test plug. Check for gas leaks.
NPT Test Plug
Figure 13 -
Manual Control Pressure
Test Point Location
65D2035

MILLIVOLT CONTROL

Figure 14
The valve regulator controls the burner pressure which
should be checked at the pressure test point.
Turn captured screw counter clockwise two or thre turns
and then place tubing to pressure gauge over test point
(Use test point "OUT" closest to control knob). After tak-
ing pressure reading, be sure and turn captured screw
clockwise fi rmly to re-seal. Do not over torque. Check for
gas leaks.
Figure 14 -
Millivolt Control Pressure
Test Point Location
FP2499
Test Port "Out"
PH Gas Logs
FP2372
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ph18

Table of Contents