9-2-7. Sensing of Frosting and Release of Defrosting
Non-stop defrosting
Outdoor fan ON
4-way valve Heating mode
Frosting is assumed according to the outdoor
temp., outdoor
heat exchanger
temp.,and
operation time.
Compressor
Outdoor fan
Indoor fan
4-way valve
Outdoor heating exchanger temp. is over 14°C.
Defrosting operation lasts 12 minutes (maximum).
2 minutes after it is stopped, compressor is ON.
4-way valve is Heating mode. Outdoor fan is ON.
EM Valve
If the air conditioner is turned off during the defrosting cycle, it will continue defrosting and turn
NOTE
itself off after defrosting is completed.
9-2-8. CT (Peak current cut-off control)
This function prevents the circuit breaker or fuse from operating to open the circuit. This function works when
electrical current has increased due to an increase in the cooling / heating load, or to a decrease in the power
supply voltage. In these cases, operation frequency is reduced or operation is interrupted automatically to con-
trol the electrical current for operation.
When the cause of the increase in electrical current is rectified, the system will resume operation in the original
mode.
Operation at 230V
Peak current cut-off trips
Normal
Hz down
Amperage
Electrical current setting for Cooling operation is used during Defrosting operation.
NOTE
Defrosting Sequence
Heating operation
Frost sensing
Outdoor heat exchanger temp.
Frosting
area
Non-stop defrosting
ON
OFF
OFF
Heating mode
Releasing of defrosting
OFF
Cooling • Dry
10.0
8.7
5.0
0
Ambient temp.
EM Valve
ON
(A)
Heating
8.7
6.0
27