Page 1
TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : SAP-CMRV1426EH FILE NO. SAP-CMRV1926EH SAP-CMRV1936EH SAP-CMRV2446EH SAP-CMRV3146EH Destination: Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity Outdoor Model No. Product Code No. 4.0kW SAP-CMRV1426EH-F 1 852 355 43 5.6kW SAP-CMRV1926EH-F 1 852 355 44 5.6kW...
Page 2
Important! When Transporting Please Read Before Starting Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees This air conditioning system meets strict safety and when lifting to reduce strain on your back. Sharp edges or operating standards.
Table of Contents Page APPLICABLE INDOOR UNITS ....................1. OPERATING RANGE ........................2. SPECIFICATIONS 2-1. Unit Specifications ......................2-2. Major Component Specifications ..................2-3. Other Component Specifications ..................3. DIMENSIONAL DATA ........................4. REFRIGERANT FLOW DIAGRAM 4-1. Refrigerant Flow Diagram ....................
Page 4
Page APPENDIX A INSTALLATION INSTRUCTIONS ................(SAP-CMRV1426EH) APPENDIX B INSTALLATION INSTRUCTIONS ................SAP-CMRV1926EH, SAP-CMRV1936EH SAP-CMRV2446EH, SAP-CMRV3146EH APPENDIX C UNIT COMBINATION TABLES .................
1. OPERATING RANGE Outdoor Unit : SAP-CMRV1426EH, SAP-CMRV1926EH, SAP-CMRV1936EH SAP-CMRV2446EH, SAP-CMRV3146EH Indoor Unit : SAP-KRV96EHDSA, SAP-KRV126EHDS SAP-KMRV76EH, SAP-KMRV96EH, SAP-KMRV126EH SAP-KRV186EH, SAP-KRV246EH Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Maximum 32 °C D.B. / 23 °C W.B. 43 °C D.B.
1. The values shown in perfromance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Table" in this manual. Indoor Unit: SAP-KMRV96EH 2units Outdoor Unit: SAP-CMRV1426EH 1unit 2. Rating conditions are: Cooling: Indoor air temp. 27°C D.B. / 19°C W.B.
Page 8
SAP-CMRV1926EH Outdoor Unit Indoor Unit SAP-KMRV96EH 1 + SAP-KRV186EH × × Type 2-Room Multi Outdoor Unit Number of Connectable Indoor Units Number of Operatable Indoor Units Max. Capacity of Operating Indoor Units 8.65 Power Source 220 to 240V Single-Phase 50Hz Voltage Rating 230V Performance...
Page 9
SAP-CMRV1936EH Outdoor Unit Indoor Unit SAP-KMRV96EH × Type 3-Room Multi Outdoor Unit Number of Connectable Indoor Units Number of Operatable Indoor Units Max. Capacity of Operating Indoor Units 10.5 Power Source 220 to 240V Single-Phase 50Hz Voltage Rating 230V Performance Cooling Heating Capacity...
Page 10
SAP-CMRV2446EH Outdoor Unit Indoor Unit SAP-KMRV96EH × Type 4-Room Multi Outdoor Unit Number of Connectable Indoor Units Number of Operatable Indoor Units Max. Capacity of Operating Indoor Units 13.1 Power Source 220 to 240V Single-Phase 50Hz Voltage Rating 230V Performance Cooling Heating Capacity...
Page 11
SAP-CMRV3146EH Outdoor Unit Indoor Unit SAP-KMRV96EH × Type 4-Room Multi Outdoor Unit Number of Connectable Indoor Units Number of Operatable Indoor Units Max. Capacity of Operating Indoor Units 14.7 Power Source 220 to 240V Single-Phase 50Hz Voltage Rating 230V Performance Cooling Heating Capacity...
2-2. Major Component Specifications 2-2-1. Outdoor Unit SAP-CMRV1426EH Outdoor Unit Control PCB Part No. CB-CMRV1426EH Controls Microprocessor Control Circuit Fuse 250V 25A Compressor Type DC Twin Rotary (Hermetic) Compressor Model / Nominal Output C-6RVN93H0M / 1,000W Compressor Oil ... Amount FV50S ...
Page 13
SAP-CMRV1926EH Outdoor Unit Control PCB Part No. CB-CMRV1926EH Controls Microprocessor Control Circuit Fuse 250V 25A Compressor Type DC Twin Rotary (Hermetic) Compressor Model / Nominal Output 5KD240XAB21 / 1,700W Compressor Oil ... Amount FV50S ... 900 Coil Resistance (Ambient Temp. 20 °C) U - V : 0.720 V - W : 0.708 W - U : 0.726...
Page 14
SAP-CMRV1936EH Outdoor Unit Control PCB Part No. CB-CMRV1935EHFA Controls Microprocessor Control Circuit Fuse 250V 25A Compressor Type DC Twin Rotary (Hermetic) Compressor Model / Nominal Output 5KD240XAB21 / 1,700W Compressor Oil ... Amount FV50S ... 900 Coil Resistance (Ambient Temp. 20 °C) U - V : 0.720 V - W : 0.708 W - U : 0.726...
Page 15
SAP-CMRV2446EH Outdoor Unit Control PCB Part No. CB-CMRV2445EHFA Controls Microprocessor Control Circuit Fuse 250V 25A Compressor Type DC Twin Rotary (Hermetic) Compressor Model / Nominal Output 5KD240XAB21 / 1,700W Compressor Oil ... Amount FV50S ... 900 Coil Resistance (Ambient Temp. 20 °C) U - V : 0.720 V - W : 0.708 W - U : 0.726...
Page 16
SAP-CMRV3146EH Outdoor Unit Control PCB Part No. CB-CMRV3145EHFA Controls Microprocessor Control Circuit Fuse 250V 25A Compressor Type DC Twin Rotary (Hermetic) Compressor Model / Nominal Output 5JD420XAB22 / 3,000W Compressor Oil ... Amount FV50S ... 1,200 Coil Resistance (Ambient Temp. 20 °C) U - V : 0.435 V - W : 0.441 W - U : 0.452...
3. DIMENSIONAL DATA Outdoor Unit SAP-CMRV1426EH Narrow tube service valve dia.6.35 (1/4") × Wide tube service valve dia.9.52 ( 3/8" ) × Unit: mm (852-0-0010-10700-0)
Page 19
Outdoor Unit SAP-CMRV1926EH Narrow tube service valve dia.6.35 (1/4") × Wide tube service valve dia.9.52 ( 3/8" ) × Unit: mm (852-0-0010-13400-0)
Page 20
Outdoor Unit SAP-CMRV1936EH Narrow tube service valve dia.6.35 (1/4") × Wide tube service valve dia.9.52 ( 3/8" ) × Unit: mm (852-0-0010-10900-0)
Page 21
Outdoor Unit SAP-CMRV2446EH Wide tube service valve dia.12.70 (1/2") × Narrow tube service valve dia.6.35 (1/4") × Wide tube service valve dia.9.52 ( 3/8" ) × Unit: mm (852-0-0010-11000-0)
Page 22
Outdoor Unit SAP-CMRV3146EH Wide tube service valve dia.12.70 (1/2") × Narrow tube service valve dia.6.35 (1/4") × Wide tube service valve dia.9.52 ( 3/8" ) × Unit: mm (852-0-0010-11100-0)
4. REFRIGERANT FLOW DIAGRAM 4-1. Refrigerant Flow Diagram Outdoor Unit SAP-CMRV1426EH Indoor unit Outdoor unit Main Service valve on accumulator accumulator wide tube Wide tube O.D.9.52mm Muffler O.D.9.52mm 4-way valve Defrost valve for hot gas bypass Capillary Electric tube for...
Page 24
Outdoor Unit SAP-CMRV1926EH Indoor unit Outdoor unit Main Service valve on accumulator accumulator wide tube Wide tube O.D.9.52mm O.D.9.52mm Header 4-way valve Defrost valve for hot gas bypass Electric expansion valve Service valve on narrow tube Narrow tube O.D.6.35mm Cooling cycle Heating cycle O.D.6.35mm Strainer...
Page 25
Outdoor Unit SAP-CMRV1936EH Indoor unit Outdoor unit Main Service valve on accumulator accumulator wide tube Wide tube O.D.9.52mm O.D.9.52mm O.D.9.52mm Header 4-way valve Defrost valve for hot gas bypass Electric expansion valve Service valve on narrow tube Narrow tube O.D.6.35mm O.D.6.35mm Cooling cycle Heating cycle...
Page 26
Outdoor Unit SAP-CMRV2446EH Indoor unit Outdoor unit Service valve on Main wide tube accumulator accumulator Wide tube O.D.9.52mm O.D.9.52mm O.D.9.52mm O.D.12.7mm Header 4-way valve Defrost valve for hot gas bypass Electric expansion valve Service valve on narrow tube Narrow tube O.D.6.35mm O.D.6.35mm O.D.6.35mm...
Page 27
Outdoor Unit SAP-CMRV3146EH Indoor unit Outdoor unit Service valve on Main wide tube accumulator accumulator Wide tube O.D.9.52mm O.D.9.52mm O.D.12.7mm O.D.12.7mm Header 4-way valve Defrost valve for hot gas bypass Electric expansion valve Service valve on narrow tube Narrow tube O.D.6.35mm O.D.6.35mm O.D.6.35mm...
5. PERFORMANCE DATA 5-1. Temperature Charts 5-1-1. Temperature Charts (SAP-CMRV1426EH) Outdoor Unit SAP-CMRV1426EH Indoor Unit SAP-KMRV76EH × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz)
Page 29
Outdoor Unit SAP-CMRV1426EH Indoor Unit SAP-KMRV96EH × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart...
Page 30
Outdoor Unit SAP-CMRV1426EH Indoor Unit SAP-KMRV126EH × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart...
Page 31
Outdoor Unit SAP-CMRV1426EH Indoor Unit SAP-KRV96EHDSA × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart...
Page 32
Outdoor Unit SAP-CMRV1426EH Indoor Unit SAP-KRV126EHDS × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart...
Page 33
5-1-2. Temperature Charts (SAP-CMRV1926EH) SAP-CMRV1926EH Indoor Unit SAP-KMRV76EH Outdoor Unit × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart Lo fan Hi fan...
Page 34
Outdoor Unit SAP-CMRV1926EH Indoor Unit SAP-KMRV96EH × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart Lo fan Hi fan HH fan...
Page 35
Outdoor Unit SAP-CMRV1926EH Indoor Unit SAP-KMRV126EH × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart (40.8) Lo fan Hi fan...
Page 36
Outdoor Unit SAP-CMRV1926EH Indoor Unit SAP-KRV186EH × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart HH fan Lo fan Hi fan...
Page 37
Outdoor Unit SAP-CMRV1926EH Indoor Unit SAP-KRV96EHDSA × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart Lo fan Hi fan HH fan...
Page 38
Outdoor Unit SAP-CMRV1926EH Indoor Unit SAP-KRV126EHDS × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart (40.8) Lo fan Hi fan...
Page 39
5-1-3. Temperature Charts (SAP-CMRV1936EH) Outdoor Unit SAP-CMRV1936EH Indoor Unit SAP-KMRV76EH × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart Lo fan Hi fan...
Page 40
Outdoor Unit SAP-CMRV1936EH Indoor Unit SAP-KMRV96EH × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart Lo fan Hi fan HH fan...
Page 41
Outdoor Unit SAP-CMRV1936EH Indoor Unit SAP-KMRV126EH × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart (40.8) Lo fan Hi fan...
Page 42
Outdoor Unit SAP-CMRV1936EH Indoor Unit SAP-KRV186EH × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart HH fan Lo fan Hi fan...
Page 43
Outdoor Unit SAP-CMRV1936EH Indoor Unit SAP-KRV96EHDSA × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart Lo fan Hi fan HH fan...
Page 44
Outdoor Unit SAP-CMRV1936EH Indoor Unit SAP-KRV126EHDS × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart (40.8) Lo fan Hi fan...
Page 45
5-1-4. Temperature Charts (SAP-CMRV2446EH) Outdoor Unit SAP-CMRV2446EH Indoor Unit SAP-KMRV76EH × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart Lo fan Hi fan...
Page 46
Outdoor Unit SAP-CMRV2446EH Indoor Unit SAP-KMRV96EH × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart Lo fan Hi fan HH fan...
Page 47
Outdoor Unit SAP-CMRV2446EH Indoor Unit SAP-KMRV126EH × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart (40.8) Lo fan Hi fan...
Page 48
Outdoor Unit SAP-CMRV2446EH Indoor Unit SAP-KRV186EH × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart HH fan Lo fan Hi fan...
Page 49
Outdoor Unit SAP-CMRV2446EH Indoor Unit SAP-KRV246EH × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart Lo fan Hi fan HH fan...
Page 50
Outdoor Unit SAP-CMRV2446EH Indoor Unit SAP-KRV96EHDSA × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart Lo fan Hi fan HH fan...
Page 51
Outdoor Unit SAP-CMRV2446EH Indoor Unit SAP-KRV126EHDS × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart (40.8) Lo fan Hi fan...
Page 52
5-1-5. Temperature Charts (SAP-CMRV3146EH) Outdoor Unit SAP-CMRV3146EH Indoor Unit SAP-KMRV76EH × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart (35.7) Lo fan...
Page 53
Outdoor Unit SAP-CMRV3146EH Indoor Unit SAP-KMRV96EH × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart (35.7) Lo fan Hi fan...
Page 54
Outdoor Unit SAP-CMRV3146EH Indoor Unit SAP-KMRV126EH × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart (35.7) Lo fan Hi fan...
Page 55
Outdoor Unit SAP-CMRV3146EH Indoor Unit SAP-KRV186EH × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart (35.7) Lo fan Hi fan...
Page 56
Outdoor Unit SAP-CMRV3146EH Indoor Unit SAP-KRV246EH × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart (35.7) Lo fan Hi fan...
Page 57
Outdoor Unit SAP-CMRV3146EH Indoor Unit SAP-KRV96EHDSA × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart (35.7) Lo fan Hi fan...
Page 58
Outdoor Unit SAP-CMRV3146EH Indoor Unit SAP-KRV126EHDS × Cooling Characteristics Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (RH : 85%, Indoor fan speed : High fan) (230V, 50Hz) (230V, 50Hz) (1) Low pressure performance chart (1) High pressure performance chart (35.7) Lo fan Hi fan...
6. ELECTRICAL DATA 6-1. Electric Wiring Diagrams Outdoor Unit SAP-CMRV1426EH To avoid electrical shock hazard, be sure to WARNING disconnect power before checking, servicing and/or cleaning any electrical parts. 8FA2-5257-56900-2...
Page 60
Outdoor Unit SAP-CMRV1926EH To avoid electrical shock hazard, be sure to WARNING disconnect power before checking, servicing and/or cleaning any electrical parts. 8FA2-5257-84200-0...
Page 61
Outdoor Unit SAP-CMRV1936EH To avoid electrical shock hazard, be sure to WARNING disconnect power before checking, servicing and/or cleaning any electrical parts. 8FA2-5257-57000-0...
Page 62
Outdoor Unit SAP-CMRV2446EH To avoid electrical shock hazard, be sure to WARNING disconnect power before checking, servicing and/or cleaning any electrical parts. 8FA2-5257-57100-0...
Page 63
Outdoor Unit SAP-CMRV3146EH To avoid electrical shock hazard, be sure to WARNING disconnect power before checking, servicing and/or cleaning any electrical parts. 8FA2-5257-89000-0...
7. FUNCTIONS 7-1. Explanation of Functions The numerical values such as temperature, frequency, time and current in parentheses are an example NOTE of SAP-CMRV3146EH and the values are different from the other models. Control/conditions Unit operation Explanation INITIAL Breaker is ON. Power is supplied to the indoor and outdoor unit control circuits, however the unit remains stopped.
Page 65
Control/conditions Unit operation Explanation HEAT Non-stop defrost When defrost operation Defrost operation begins based on outdoor heat begins, frost has formed exchanger temperature and outdoor air on the outdoor unit temperature conditions. Non-stop defrost (Refer to Fig. 1) (when the ambient air Indoor fan : Stopped temperature is low).
Page 66
Control/conditions Unit operation Explanation COOL The ON/OFF operation The operation lamp illuminates. The outdoor unit does not operate for 3 minutes button on the remote even after the breaker is turned ON. The indoor fan operates at the set fan speed. controller is pressed.
Page 67
(1/f fluctuation fan) Control/conditions Unit operation Explanation SENSOR The ON/OFF operation The operation lamp illuminates. The outdoor unit does not operate for 3 minutes button on the remote even after the breaker is turned ON. The indoor fan operates at the set fan speed. controller is pressed.
7-2. Protective Functions The numerical values such as temperature, frequency, time and current in parentheses are an example NOTE of SAP-CMRV3146EH and the values are different from the other models. 7-2-1. Defrost Detection and Release (1) Non-stop defrosting Defrosting sequence 4-way valve ON Defrost detection occurs in either of the following cases: •...
Page 69
7-2-2. Current Control The operating current may rise as a result of causes including increasing heating or cooling loads or decreases in power voltage. In these cases, the operating frequency is automatically reduced, or operation is stopped, in order to control the operating current so that it is (20 A) or less.
Page 70
7-2-3. Low Start Current Operation starts at (8 Hz), and the start current is less than the normal operating current. This prevents the flickering of fluorescent lights or television screens that occurs when ordinary A/C units start. 7-2-4. Compressor Temperature Control To protect the compressor coil from overheating, the operating frequency is controlled based on the compressor discharge temperature.
8. TROUBLESHOOTING 8-1. Precautions before Performing Inspection or Repair Both the indoor unit and outdoor unit include electronic control circuits. Be sure to pay attention to the following before inspecting or repairing the outdoor- side electronic circuits. High-capacity electrolytic capacitors are used inside the outdoor unit controller (inverter). They retain an electrical charge (charging voltage DC 311 V) even after the power is turned OFF, and some time is required for the charge to dissipate.
8-2. Trouble Diagnosis by Error Monitor Lamps To prevent electric shock, do not inspect or repair until WARNING the Power Lamp on the P.C.Board is turned off. 8-2-1. Location of the Error Monitor Lamps Remove the top plate of outdoor unit and the cover of Electrical Component Box. The Power Lamp and Error Monitor Lamps are located on the P.C.Board of Electrical Component Box.
8-3. Checking the Outdoor System 8-3-1. Checking the outdoor unit Work procedure Check items (unit operation) • Apply 220 V AC between terminals L and N on the • The LED (red) on the control board must illuminate. outdoor unit terminal plate. •...
8-4. Trouble Diagnosis of Each Part 8-4-1. Problems of Each Part and Inspection Points For details about the inspection points, refer to the Inspection Points for Each Part. Indoor unit Outdoor unit Others Problems No. of Inspection Points for Each part Inspection points Self-Diagnostics check...
Page 75
When the power is turned ON, the needle will move in the following seguence in approximately 10 to 20 seconds for No voltage on circuit board Voltage varies each point. Model No. Sequence SAP-CMRV1426EH SAP-CMRV1926EH SAP-CMRV1936EH SAP-CMRV2446EH SAP-CMRV3146EH Check the coil resistance. Check the illumination Check the resistance between the gray lead of the red Power Lamp.
Page 76
(8) Branch tubing temperature sensor Check that the sensor is securely contained in the thermostat holder. (9) Breaker Check whether or not the breaker has been tripped. Check that the breakers and fuses used are of the specified capacity. Check that the breaker and its line are exclusive for A/C use. (10) Refrigerant gas pressure Start a COOL test run, and messure the temperatures of the A/C intake air and discharge air.
Any one of the above measured values is not normal. Outdoor unit controller trouble (Replace the controller .) (Reference) DC motor connector pin arrangement SAP-CMRV1926EH / -CMRV1936EH SAP-CMRV1426EH SAP-CMRV2446EH / -CMRV3146EH Pin 1: Vs (white) Pin 1: Vm (red) Pin 2: Not used Pin 2: Not used...
9. REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN SERVICING UNIT 9-1. Characteristics of New Refrigerant R410A 9-1-1. What is New Refrigerant R410A? R410A is a new refrigerant that contains two types of pseudo-non-azeotropic refrigerant mixture. Its refrigeration capacity and energy efficiency are about the same level as the conventional refrigerant, R22. 9-1-2.
Page 79
Tubing precautions Refrigerant R410A is more easily affected by dust or moisture compared with R22, thus be sure to temporarily cover the ends of the tubing with caps or tape prior to installation. Never use 0.7mm-thick copper tubing or tubing which is less than 0.8mm in thickness, since air conditioners with R410A are subject to higher pressure than those using R22 and R407C.
9-3. Tools Specifically for R410A For servicing, use the following tools for R410A Tool Distinction Tool Name Gauge manifold Charging hose Gas leak detector Refrigerant cylinder Charging cylinder Refrigerant recovery unit Vacuum pump with anti-reverse flow (*1) Tools specifically for R410A (Solenoid valve-installed type, which prevents oil from flowing back into the unit when the power is off, is recommended.) Vacuum pump (*2)...can be used if the following adapter is attached.
9-5. In Case of Compressor Malfunction Should the compressor malfunction, be sure to make the switch to a replacement CAUTION compressor as quickly as possible. Use only the tools indicated exclusively for R410A. See "9-3. Tools Specifically for R410A." 9-5-1. Procedure for Replacing Compressor (1) Recovering refrigerant Any remaining refrigerant inside the unit should not be (1) Recover refrigerant...
Page 82
(5) Recharging Configuration and characteristics of cylinders Be sure to charge the specified amount of Valve refrigerant in liquid state using the service port of the wide tube service valve. The proper amount is listed on the unit's nameplate. When the entire amount cannot be charged all at once, charge gradually while operating the unit in Cooling Operation.
9-6. In Case Refrigerant is Leaking Never attempt to charge additional refrigerant when refrigerant has been leaking CAUTION from the unit. Follow the procedure described below to locate points of leaks and carry out repairs, then recharge the refrigerant. (1) Detecting Leaks Use the detector for R410A to locate refrigerant leak points.
9-7. Charging Additional Refrigerant 9-7-1. When Tubes are Extended Observe the proper amount of refrigerant as stated in this service manual or the installation manual that came with the indoor unit. Charge additional refrigerant in liquid state only. Never charge additional refrigerant if refrigerant is leaking from the unit. Follow CAUTION instructions given in "9-6.
Page 85
APPENDIX A INSTALLATION INSTRUCTIONS SAP-CMRV1426EH (II-852-6-4190-456-00-1) NOTE The specifications of SAP-KRV96EHDSA are the same as those of SAP-KRV96EHDS described in the Installation Instruction.
Page 87
IMPORTANT! Please Read Before Starting outdoor units. Get a partner to help, and bend your knees This air conditioning system meets strict safety and operat- when lifting to reduce strain on your back. Sharp edges or ing standards. As the installer or service person, it is an thin aluminum fins on the air conditioner can cut your fin- important part of your job to install or service the system so gers.
Page 88
1. General 5. Carpenter’s level This booklet briefly outlines where and how to install 6. Sabre saw or key hole saw the air conditioning system. Please read over the 7. Hacksaw entire set of instructions for the indoor and outdoor 8.
Page 89
1-5. Additional Materials Required for Installation Refrigeration (armored) tape Insulated staples or clamps for connecting wire (See local codes) Putty Refrigeration lubricant Clamps or saddles to secure refrigerant tubing Indoor unit 2. Installation Site Selection 2-1. Indoor Unit To prevent abnormal heat generation WARNING and the possibility of fire, do not place obstacles, enclosures and...
Page 90
install the indoor unit more than 1 meter away from any antenna or power lines or connecting wires used for tele- vision, radio, telephone, security system, or intercom. Electrical noise from any of these sources may affect operation. install in a sturdy manner to avoid increased operating noise.
Page 91
2-3. Outdoor Unit Exhaust fan AVOID: Hot air heat sources, exhaust fans, etc. (Fig. 5a) Heat source damp, humid or uneven locations. Outdoor unit position the outdoor unit in a protected location where snow will not blow into it. choose a place as cool as possible. Fig.
Page 92
2-4. Outer Dimensions of Outdoor Unit Service valve on narrow tube side (Outer diameter ø 6.35 ) Service valve on wide tube side (Outer diameter ø 9.52 ) unit: mm Fig. 6a Diagram of Outdoor Unit Installation 2-5. Never install only a single indoor unit. Be sure to connect indoor and outdoor units only in combinations that are listed in the catalog or in the combination table that was provided with the outdoor unit.
Page 93
3. Installation Process Embedding the Tubing and Wiring 3-1. Do not connect tubes to locations that are embedded. Be sure to bind refrigerant tubing and inter-unit cables together with vinyl tape. The power cable must be obtained on-site. (ø3.5: Less than 26 m) Be sure to apply the provided labels to both ends of the inter-unit cables to prevent miswiring.
Page 94
NOTE Copper tubing When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube. (Fig. 9) (3) Remove the flare nut from the unit and be sure to mount Reamer it on the copper tube. (4) Make a flare at the end of copper tube with a flare tool.* (Figs.
Page 95
Torque wrench Be sure to match refrigerant CAUTION tubing and electric wiring between indoor and outdoor Spanner units. Indoor unit Outdoor unit Fig. 15 3-7. Insulation of Refrigerant Tubing IMPORTANT To prevent heat loss and wet floors due to dripping of con- Insulation densation, both tubes must be well insulated with a proper insulation material.
Page 96
4. Air Purging Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. Therefore, they must be purged completely. pressure in the system rises operating current rises cooling efficiency drops moisture in the air may freeze and block capillary tubing Service valve on...
Page 97
(4) With the “Lo” knob of the manifold valve open and high-pressure valve (“Hi”) closed completely, run the vacuum pump. Run the pump until the pres- sure is –101 kPa (–76 cmHg). The operation time for the vacuum pump varies with tubing length and the capacity of the pump.
Page 98
(11) Replace the flare nut on the wide tube service port and fasten the flare nut securely with an adjustable wrench or box wrench. Next, mount the valve cap and tighten it with a torque wrench (the cap needs to be tightened with the torque of 20 N·m (200 kgf ·...
Page 99
5. Wiring Instructions 5-1. General Precautions on Wiring (1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. (2) Provide a power outlet to be used exclusively for each unit, with a power supply disconnect and circuit break- er for overcurrent protection provided in the exclusive line.
Page 100
WARNING WARNING To avoid the risk of electric shock, each air Be sure to comply with local codes on running conditioner unit must be grounded. the wire from the indoor unit to the outdoor unit For the installation of a grounding device, (size of wire and wiring method, etc.).
Page 101
5-4. How to Connect Wiring to the Terminal Loose wiring may cause the WARNING terminal to overheat or result in unit malfunction. A fire hazard may also exist. There- fore, be sure all wiring is tightly connected. When connecting each power wire to the corresponding terminal, follow the instructions “How to connect wiring 7 mm (ACTUAL STRIP...
Page 102
5-5. Wiring Instructions for the Outdoor Unit CAUTION Be sure to correctly align inter-unit cables A and B. Outdoor unit A Terminal board 1 2 3 4 5 6 7 8 Power: Single-phase, 220/240VAC 50HZ Power switch Indoor unit A (not provided) A is the indoor unit with Terminal board...
Page 103
Regulations on wire size differ from locality to locality. Cabinet For field wiring requirements, please refer to your local electrical codes. Make sure that the installation fully complies with all local and national regulations. (1) Remove access panel “C”. (Fig. 32) (2) Connect the inter-unit wiring and power line according to the drawing on the panel side.
Page 104
7. Connecting a Home Automation Device The HA (white) 4P terminal is located on the indoor unit PCB. If a HA device will be used, connect it to this terminal. Also, refer to Section 9. Electric Wiring Diagram in the outdoor unit installation manual. 8.
Page 105
SAP-KRV96/126EHDS SAP-KMRV76/96/126EH EVAPORATOR TERMINAL BASE FERRITE CORE + + + + GRN/YEL EVAPORATOR EARTH PLATE FLAP MOTOR AC IN SI-2 FLAP MOTOR AC IN-2 (UPPER) FLAP FLAP 5P(WHT) (RED) THERMISTOR LAMP CONNECTOR (ROOM) 9P(WHT) (WHT) (WHT) THERMISTOR (COIL) CONTROLLER THERMISTOR (HUM) FAN MOTOR (WHT)
Page 106
APPENDIX B INSTALLATION INSTRUCTIONS SAP-CMRV1926EH SAP-CMRV1936EH SAP-CMRV2446EH SAP-CMRV3146EH (II-852-6-4190-442-00-2) NOTE The specifications of SAP-KRV96EHDSA are the same as those of SAP-KRV96EHDS described in the Installation Instruction.
IMPORTANT! when lifting to reduce strain on your back. Sharp edges or Please Read Before Starting thin aluminum fins on the air conditioner can cut your fin- gers. This air conditioning system meets strict safety and oper- When Installing… ating standards. As the installer or service person, it is an important part of your job to install or service the system …In a Ceiling or Wall so it operates safely and efficiently.
1. General 5. Carpenter’s level This booklet briefly outlines where and how to install 6. Sabre saw or key hole saw the air conditioning system. Please read over the entire 7. Hacksaw set of instructions for the indoor and outdoor units and 8.
1-5. Additional Materials Required for Installation Refrigeration (armored) tape Insulated staples or clamps for connecting wire (See local codes) Putty Refrigeration lubricant Clamps or saddles to secure refrigerant tubing Indoor unit 2. Installation Site Selection 2-1. Indoor Unit To prevent abnormal heat generation WARNING and the possibility of fire, do not place obstacles, enclosures and...
install the indoor unit more than 1 meter away from any antenna or power lines or connecting wires used for tele- vision, radio, telephone, security system, or intercom. Electrical noise from any of these sources may affect operation. install in a sturdy manner to avoid increased operating noise.
2-3. Outdoor Unit Exhaust fan AVOID: Hot air heat sources, exhaust fans, etc. (Fig. 5a) Heat source damp, humid or uneven locations. Outdoor unit position the outdoor unit in a protected location where snow will not blow into it. choose a place as cool as possible. Fig.
2-4. Outer Dimensions of Outdoor Unit (1) SAP-CMRV1926 Service valve on narrow tube side (Outer diameter ø 6.35 ) Service valve on wide tube side (Outer diameter ø 9.52 ) Fig. 6a (2) SAP-CMRV1936 Service valve on narrow tube side (Outer diameter ø...
Diagram of Outdoor Unit Installation 2-5. Never install only a single indoor unit. Be sure to connect indoor and outdoor units only in combinations that are listed in the catalog or in the Indoor unit D combination table that was provided with the outdoor unit. (Use caution.
3. Installation Process Embedding the Tubing and Wiring 3-1. Do not connect tubes to locations that are embedded. Be sure to bind refrigerant tubing and inter-unit cables together with vinyl tape. The power cable must be obtained on-site. (ø3.5: Less than 26 m) Be sure to apply the provided labels to both ends of the inter-unit cables to prevent miswiring.
NOTE Copper tubing When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube. (Fig. 9) (3) Remove the flare nut from the unit and be sure to mount Reamer it on the copper tube. (4) Make a flare at the end of copper tube with a flare tool.* (Figs.
Torque wrench Be sure to match refrigerant CAUTION tubing and electric wiring between indoor and outdoor Spanner units. Indoor unit Outdoor unit Fig. 15 3-7. Insulation of Refrigerant Tubing IMPORTANT To prevent heat loss and wet floors due to dripping of con- Insulation densation, both tubes must be well insulated with a proper insulation material.
4. Air Purging Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. Therefore, they must be purged completely. Service valve on pressure in the system rises narrow Manifold gauge operating current rises tube side (special for R410A) Service High-pressure valve cooling efficiency drops...
Page 123
(4) With the “Lo” knob of the manifold valve open and high-pressure valve (“Hi”) closed completely, run the vacuum pump. Run the pump until the pres- sure is –101 kPa (–76 cmHg). The operation time for the vacuum pump varies with tubing length and the capacity of the pump.
(11) Replace the flare nut on the wide tube service port and fasten the flare nut securely with an adjustable wrench or box wrench. Next, mount the valve cap and tighten it with a torque wrench (the cap needs to be tightened with the torque of 20 N·m (200 kgf ·...
5. Wiring Instructions 5-1. General Precautions on Wiring (1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. (2) Provide a power outlet to be used exclusively for each unit, with a power supply disconnect and circuit break- er for overcurrent protection provided in the exclusive line.
WARNING WARNING To avoid the risk of electric shock, each air Be sure to comply with local codes on running conditioner unit must be grounded. the wire from the indoor unit to the outdoor unit For the installation of a grounding device, (size of wire and wiring method, etc.).
5-4. How to Connect Wiring to the Terminal Loose wiring may cause the WARNING terminal to overheat or result in unit malfunction. A fire hazard may also exist. There- fore, be sure all wiring is tightly connected. When connecting each power wire to the corresponding terminal, follow the instructions “How to connect wiring 7 mm (ACTUAL STRIP...
5-5. Wiring Instructions for the Outdoor Unit CAUTION Be sure to correctly align inter-unit cables A, B, C and D. Outdoor unit Terminal board Indoor unit A 1 2 3 4 5 6 7 8 9 10 11 12 Power: A is the indoor unit with Terminal board refrigerant tubing that is...
Regulations on wire size differ from locality to locality. Cabinet For field wiring requirements, please refer to your local electrical codes. Make sure that the installation fully complies with all local and national regulations. (1) Remove access panel “C”. (Fig. 32) (2) Connect the inter-unit wiring and power line Access panel C according to the drawing on the panel side.
7. Connecting a Home Automation Device The HA (white) 4P terminal is located on the indoor unit PCB. If a HA device will be used, connect it to this terminal. Also, refer to Section 9. Electric Wiring Diagram in the outdoor unit installation manual. 8.
Page 131
SAP-KRV184/244EH SAP-KMRV76/96/126EH EVAPORATOR EVAPORATOR TERMINAL BASE FERRITE CORE TERMINAL BASE FLAP MOTOR AC1 AC2 SI CONNECTOR AC IN SI-2 AC IN-2 FLAP FLAP FLAP FLAP 5P(WHT) 5P(WHT) LAMP 10P( WHT ) FLAP MOTOR LAMP CONNECTOR 9P(WHT) CONTROLLER CONTROLLER ROOM THERMISTOR FAN MOTOR ROOM/COIL 4P( WHT )
Page 132
Outdoor Unit Unidad exterior Appareil extérieur Außengerät Unità Esterna Unidade exterior ∂ ∂ Í Í ˆ ˆ Ù Ù Â Â Ú Ú È È Î Î ‹ ‹ Ì Ì Ô Ô Ó Ó ¿ ¿ ‰ ‰ · · SAP-CMRV1926EH COIL COIL...
Page 135
UNIT COMBINATION TABLES < > List of Combination Table Name of Combination Table Model No. of Outdoor Unit Remarks 2-Room Outdoor Unit Combination Table SAP-CMRV1426EH OI-852-6-4181-076-00-1 2-Room Outdoor Unit Combination Table SAP-CMRV1926EH OI-852-6-4181-040-00-2 3-Room Outdoor Unit Combination Table SAP-CMRV1936EH OI-852-6-4181-041-00-2...
Page 136
Otherwise, the air conditioner may not run properly and trouble may occur. Example: When two indoor units are connected If the following holds true • Rated cooling capacity of SAP-CMRV1426EH outdoor unit: C=4 (kW) • Rated cooling capacity of indoor units: K1, K2, ... (kW) Then: C x 2 (200%) K1 + K2 + ..
Page 137
< Combinations of operatable indoor units > SAP-CMRV1426EH NOTE (Rated cooling capacity: 4.0 kW) 2.2: SAP-KMRV74/76EH 2.65: SAP-KMRV94/96EH 3.5: SAP-KMRV124/126EH Table 1 Indoor Unit Capacity (kW) COOLING HEATING Indoor Unit Combination Room Room Total Performance Room Room Total Performance Capacity ( Min. - Max. ) Capacity ( Min.