Sanyo SAP-KRV91EH Technical & Service Manual page 21

Inverter split system air conditioner
Hide thumbs Also See for SAP-KRV91EH:
Table of Contents

Advertisement

7-1-2. Outdoor Unit
AVOID:
heat sources, exhaust fans, etc. (Fig. 4)
damp, humid or uneven locations.
DO:
choose a place as cool as possible.
choose a place that is well ventilated.
allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 5a)
provide a solid base (level concrete pad, concrete
× 40 cm beams or equal), a minimum of
block, 10
10 cm above ground level to reduce humidity and
protect the unit against possible water damage
and decreased service life. (Fig. 5a)
Install cushion rubber under unit's feet to reduce
vibration and noise. (Fig. 5b)
use lug bolts or equal to bolt down unit, reducing
vibration and noise.
NO
Hot air
Outdoor unit
Air intake
Min. 10 cm
Min.
Air discharge
5 cm
Air intake
Concrete
or equal
17
Exhaust fan
Heat source
Fig. 4
Obstacle above
Valve
side
Min.
25 cm
Min.
40 cm
Ground
Fig. 5a
Cushion rubber
Fig. 5b
Min.
Min.
2 m
2 m
Min. 10 cm
Air intake
Anchor bolts
(4 pcs.)
Min. 10 cm