Dhw/Group 3 - Viessmann VITODENS 200-W Service Instructions Manual

Table of Contents

Advertisement

DHW/Group 3

Coding in the delivered condition
5b:0
DHW cylinder directly
connected to the boiler
5E:0
Circulation pump for cyl-
inder heating stays in
control mode at signal
"External blocking"
5F:0
Circulation pump for cyl-
inder heating stays in
control mode at signal
"External demand"
60:20
During DHW heating, the
boiler water temperature
is max. 20 K higher than
the set DHW tempera-
ture
62:2
Circulation pump with
2 min run-on time after
cylinder heating
63:0
Without auxiliary function
for DHW heating (only for
constant temperature
control units)
65:...
Information regarding the
type of diverter valve (not
adjustable):
0: No diverter valve
1: Viessmann diverter
valve
2: Wilo diverter valve
3: Grundfos diverter valve
(cont.)
Possible change
5b:1
DHW cylinder connected
downstream of the low loss
header
5E:1
Circulation pump for cylin-
der heating stops at signal
"External blocking"
5E:2
Circulation pump for cylin-
der heating starts at signal
"External blocking"
5F:1
Circulation pump for cylin-
der heating stops at signal
"External demand"
5F:2
Circulation pump for cylin-
der heating starts at signal
"External demand"
60:5
The difference between the
to
boiler water temperature
60:25
and the set DHW tempera-
ture is adjustable from 5 to
25 K
62:0
Circulation pump without
run-on
62:1
Run-on time adjustable
to
from 1 to 15 min
62:15
63:1
Auxiliary function: 1 x daily
63:2
Every 2 days to every 14
to
days
63:14
63:15
2 x daily
Code 2
65