Code 1
Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
Min. pump speed
E7:30
Minimum speed of the
variable speed heating
circuit pump: 30 % of the
maximum speed (only for
weather-compensated
control units)
Screed function
F1:0
Screed drying function
disabled (only for
weather-compensated
control units)
Party mode time limit
F2:8
Time limit for party mode
or external heating pro-
gram changeover via key:
8 h (only for weather-
compensated control
units)
Pump control in "Only DHW"
F6:25
In the "Only DHW" oper-
ating mode, the internal
circulation pump is per-
manently ON (only for
constant temperature
control units)
Party mode ends automatically in the "Heating and DHW" program, when the
*1
system changes over to operation with standard room temperature.
50
*1
Possible change
E7:0
Minimum speed adjustable
to
from 0 to 100 % of the max-
E7:100
imum speed
F1:1
Screed drying function
to
adjustable in accordance
F1:6
with 6 optional tempera-
ture/time profiles (see
page 126)
F1:15
Constant flow temperature
20 °C
F2:0
No time limit for party
mode
F2:1
Time limit adjustable from 1
to
to 12 h
F2:12
F6:0
In the "Only DHW" operat-
ing mode, the internal cir-
culation pump is perma-
nently OFF
F6:1
In the "Only DHW" operat-
to
ing mode, the internal cir-
F6:24
culation pump will be star-
ted for 10 min each time, 1
to 24 times per day.
(cont.)
*1
*1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents