Fault codes
(cont.)
Dis-
Const.
played
fault
code
E5
X
E7
X
E8
X
EA
X
Eb
X
EC
X
Ed
X
Weath.-
System char-
comp.
acteristics
X
Burner blocked Fault, flame
X
Burner in a fault
state
X
Burner in a fault
state
X
Burner in a fault
state
X
Burner in a fault
state
X
Burner in a fault
state
X
Burner in a fault
state
Troubleshooting
Cause
Measures
Replace the control
amplifier
unit.
The ionisa-
Check the ionisa-
tion current
tion electrode and
lies outside
cable.
the permissi-
Press reset button
ble range dur-
R.
ing calibra-
tion
The ionisa-
Check the ionisa-
tion current
tion electrode and
lies outside
cable.
the permissi-
Press reset button
ble range
R.
The ionisa-
Check the ionisa-
tion current
tion electrode and
lies outside
cable.
the permissi-
Press reset button
ble range dur-
R.
ing calibra-
tion
Heat draw-off
Initiate a heat
repeatedly
draw-off. Switch
too low during
the boiler OFF and
calibration
ON again.
Press reset button
R.
Parameter
Press reset button
fault during
R
calibration
or
Replace boiler cod-
ing card and press
reset button R.
Internal fault
Replace the control
unit.
101