Viessmann VITODENS 200-W Service Instructions Manual page 97

Table of Contents

Advertisement

Fault codes
(cont.)
Dis-
Const.
played
fault
code
bC
bd
bE
bF
C1
X
C2
X
C3
X
Weath.-
System char-
comp.
acteristics
X
Control mode
without remote
control
X
Control mode
without remote
control
X
Control mode
without remote
control
X
Control mode
X
Control mode
X
Control mode
X
Control mode
Troubleshooting
Cause
Measures
Communica-
Check connec-
tion error,
tions, lead, coding
remote con-
address "A0" and
trol Vitotrol
remote control set-
heating circuit
tings (see
1 (without
page 132)
mixer)
Communica-
Check connec-
tion error,
tions, lead, coding
remote con-
address "A0" and
trol Vitotrol
remote control set-
heating circuit
tings (see
2 (with mixer)
page 132)
Communica-
Check connec-
tion error,
tions, lead, coding
remote con-
address "A0" and
trol Vitotrol
remote control set-
heating circuit
tings (see
3 (with mixer)
page 132)
Incorrect
Replace the LON
LON commu-
communication
nication mod-
module
ule
Communica-
Check electrical
tion error
connections
extension
EA1
Communica-
Check solar control
tion error,
module or
solar control
Vitosolic
module or
Vitosolic
Extension
Check electrical
AM1 commu-
connections
nication error
97

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents