Troubleshooting
Fault codes
(cont.)
Dis-
Const.
played
fault
code
Fd
X
FE
X
FF
X
104
Weath.-
System char-
comp.
acteristics
X
Burner in a fault
state
X
Burner blocked
or in a fault
state
X
Burner blocked
or in a fault
state
Cause
Measures
Fault, burner
Check ignition
control unit
electrodes and
connecting cables.
Check whether a
strong interference
(EMC) field exists
near the appliance.
Press reset button
R.
Replace control
unit if the fault per-
sists.
Boiler coding
Press reset button
card or main
R. Replace boiler
PCB faulty
coding card or con-
trol unit if the fault
persists.
Internal fault
Start the appliance
or reset but-
again. Replace the
ton R
control unit if the
blocked
appliance will not
restart.