Dhw/Group "3; Solar/Group "4 - Viessmann VITODENS 200-W Installation And Service Instructions Manual

Table of Contents

Advertisement

Code 1
Boiler/group "2"
(cont.)
Coding in the delivered condition
Service interval in months
23:0
No time set for burner service in-
terval
Service status
24:0
"Service" not shown on the dis-
play
Filling/venting
2F:0
Venting program/fill program inac-
tive

DHW/group "3"

Select "DHW" for weather-compensated control unit
(see page 45).
Coding
Coding in the delivered condition
Set DHW temperature reheating suppression
67:40
For solar DHW heating: Set DHW
temperature 40 °C. Reheating is
suppressed above the selected set
temperature: Boiler only starts as
backup if the rise in the DHW tem-
perature is too low.
Cannot be adjusted on gas con-
densing combi boilers
Enable DHW circulation pump
73:0
DHW circulation pump: "ON" ac-
cording to time program (only for
weather-compensated control
units)

Solar/group "4"

Select "Solar" for weather-compensated control unit
(see page 45).
Select "4" for constant temperature control unit (see
page 45).
48
Possible change
23:1
Interval adjustable from 1 to
to
24 months
23:24
24:1
"Service" shown on the display.
The address is set automatically and
must be reset manually after a serv-
ice.
2F:1
Venting program active
2F:2
Fill program active
Select "3" for constant temperature control unit (see
page 45).
Possible change
67:0
Set DHW temperature adjustable
to
from 0 to 95 °C (limited by boiler-
67:95
specific parameters)
73:1
"ON" from once per hour for 5 min
to
up to 6 times per hour for 5 min dur-
73:6
ing the time program
73:7
Constantly "ON"
Note
The solar group is only displayed if a solar control
module, type SM1, is connected.