Commissioning, inspection, maintenance
Further details regarding the individual steps
yes
Fan starts
yes
Ignition
yes
Gas train opens
yes
Ionisation current
builds
Symbol A
yes
Burner in opera-
tion
14
no
After approx. 51 s
fault F9
no
Fault EE
no
Fault EE
no
Fault EE
no
Stops below the
set boiler water
temperature and
restarts immedi-
ately
(cont.)
Check the fan, fan
connecting cables,
power at the fan
and fan control
Check the ignition
module (control
voltage 230 V
across plugs
"X2.1" and "X2.2")
Check the gas train
(control voltage
230 V); check the
gas supply pres-
sure
Check the ionisa-
tion electrode
adjustment and the
gas line for air-
locks
Check the flue gas
system for tight-
ness (flue gas
recirculation),
check the gas flow
pressure