Viessmann VITODENS 200-W Service Instructions Manual page 76

Table of Contents

Advertisement

Code 2
Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
A6:36
Extended economy func-
tion disabled (only for
weather-compensated
control units)
A7:0
Without mixer economy
function (only for a
weather-compensated
control unit and heating
circuit with mixer)
A8:1
Heating circuit with mixer
creates a demand for the
internal circulation pump
(only for weather-com-
pensated control units)
A9:7
With pump idle time:
Heating circuit pump
"OFF" if the set value is
altered through a change
in operating mode or
through a change in the
set room temperature
(only for weather-com-
pensated control units)
76
Possible change
A6:5
Extended economy control
to
enabled, i.e. the burner and
A6:35
heating circuit pump will be
stopped and the mixer
closed at a variable value,
adjustable between 5 and
35 °C plus 1 °C. The base
value is the adjusted out-
side temperature. This
value is based on the
actual outside temperature
and a time constant that
takes the cooling down of
an average building into
consideration.
A7:1
With mixer economy func-
tion (extended heating cir-
cuit pump logic):
Heating circuit pump also
"OFF":
■ If a mixer has been
closed for longer than
20 min.
Heating pump "ON":
■ If the mixer changes to
control function
■ If there is a risk of frost
A8:0
Heating circuit with mixer
creates no demand for the
internal circulation pump
A9:0
Without pump idle time
A9:1
With pump idle time;
to
adjustable from 1 to 15
A9:15
(cont.)