Fault codes
(cont.)
Dis-
Const.
played
fault
code
93
X
94
X
98
X
99
X
9A
X
9b
X
9C
X
9E
X
Weath.-
System char-
comp.
acteristics
X
Control mode
X
No DHW heat-
ing
X
Control mode
X
Control mode
X
No DHW heat-
ing
X
Control mode
X
No DHW heat-
ing
X
Control mode
Troubleshooting
Cause
Measures
Short circuit,
Check temperature
cylinder tem-
sensor at connec-
perature sen-
tion S3 to the
sor
Vitosolic 100.
Short circuit,
Check temperature
cylinder tem-
sensor % on the
perature sen-
solar control mod-
sor
ule or the Vitosolic
sensor
Lead break,
Check sensor /
temperature
on the solar control
sensor /
module
Check sensor aÖ
Lead break,
temperature
on the solar control
sensor aÖ
module.
Lead break,
Check temperature
collector tem-
sensor & on the
perature sen-
solar control mod-
sor
ule or the Vitosolic
sensor
Lead break,
Check temperature
cylinder tem-
sensor at connec-
perature sen-
tion S3 to the
sor
Vitosolic 100.
Lead break,
Check temperature
cylinder tem-
sensor % on the
perature sen-
solar control mod-
sor
ule or the Vitosolic
sensor
No flow rate
Check solar circuit
in the collec-
pump and solar cir-
tor circuit or
cuit. Acknowledge
flow rate too
fault message.
low, or tem-
perature lim-
iter has
responded