Huawei AP8030DN Installation And Maintenance Manual page 97

Hide thumbs Also See for AP8030DN:
Table of Contents

Advertisement

Huawei AP8030DN & AP8130DN
Hardware Installation and Maintenance Guide
Take the following measures to meet the requirements:
l
l
l
l
Requirements for ESD Prevention
The absolute value of electrostatic voltage is less than 1000 V.
Take the following measures to meet the requirements:
l
l
l
l
l
l
l
Electromagnetism Requirements for the Equipment Room
All interference sources, inside or outside the equipment room, can cause equipment problems
with capacitive coupling, inductive coupling, electromagnetic wave radiation, and common
impedance (including grounding system) coupling. Prevent the interference using these
approaches:
l
l
l
l
Requirements for Lightning Proof Grounding
Table 5-13
Issue 02 (2014-12-05)
Avoid constructing the room near a place where the corrosive gas concentration is high,
such as a chemical plant.
Ensure the air intake vent of the room is in the prevailing upwind direction from the
pollution source.
Place batteries in different rooms.
A professional service should monitor the corrosive gas conditions regularly.
Train operators about ESD prevention.
Keep the correct humidity level in the equipment room to reduce the impact of static
electricity.
Lay out an ESD floor in equipment rooms.
Wear ESD shoes and clothing before entering equipment room.
Use ESD tools, such as wrist straps, tweezers, and pullers.
Ground all conductive materials in the room, including computer terminals. Use ESD
worktables.
Keep non-ESD materials (such as common bags, foams, and rubbers) at least 30 cm (11.81
in.) away from boards and ESD-sensitive components.
Take effective measures against electrical interference from the power supply system.
Do not use the working ground of the equipment as the same ground for surge protection.
Separate them as far as possible.
Keep the equipment far away from strong power radio transmitters, radar units, and high-
frequency and high-current equipment.
Use electromagnetic shielding if necessary.
shows the requirements for lightning proof grounding.