Hardware Installation and Maintenance Guide
Item
Door and
windows
Wall surface
treatment
Cable trays
Water pipe
Internal
partition wall
Installation
position of the
air conditioner
Other
requirements
Figure 5-80 Internal partition wall inside the equipment room
Equipment Room Environment
Dust on devices may cause electrostatic discharge and result in poor contact for connectors or
metal connection points. This problem can shorten the life span of devices and cause faults.
Issue 02 (2014-12-05)
Requirements
The door of the equipment room should be 2 m (6.56 ft) high and 1 m (3.28
ft) wide. One door is enough. Seal the doors and windows with dustproof
plastic tape. Use double-pane glass in the windows and seal them tightly.
Paste wallpaper on the wall or apply flat paint. Do not use pulverized paint.
Use cable trays to arrange cables. The inner faces of the cable trays must
be smooth. The reserved length and width of the cable trays, and the number,
position and dimensions of the holes must comply with the requirements
of device arrangement.
Do not pass service pipes, drainpipes, and storm sewers through the
equipment room. Do not place a fire hydrant in the equipment room, but
place it in the corridor or near the staircase.
Separate the area where the equipment is installed from the equipment room
door. The partition wall can block some outside dust.
Install air conditioner vents so that the air does not blow directly on
equipment.
Avoid the proliferation of mildew, and keep out rodents (like mice).
Huawei Proprietary and Confidential