Stove Placement Requirements; Floor Protection Requirements - Lopi Answer Owner's Manual

Residential freestanding stove • mobile-home freestanding stove • alcove approved • masonry fireplace insert • zero clearance (metal) fireplace insert
Hide thumbs Also See for Answer:
Table of Contents

Advertisement

S
P
TOVE
LACEMENT
HINT: REDUCING CLEARANCES - Clearances may be reduced by methods specified in
¥
Stove must be placed so that no combustibles are within, or can swing within (e.g. drapes,
doors), 36" of the front of the stove
¥
If the stove is placed in a location where the ceiling height is less than 7', it must follow the
requirements in the section "Alcove Installation Requirements"
¥
Must maintain the following clearances to combustibles (drywall, furniture, etc.):
D
A
* Reduced clearance installations require one of the chimneys below:
¥ DURAVENT model DVL with DURA-PLUS chimney
¥ SECURITY model DP with SECURITY model ASHT or S2100 chimney
¥ SELKIRK METALBESTOS model DS connector with model SSII chimney
¥ Standard Masonry Chimney with any one of the above listed connectors
F
P
LOOR
ROTECTION
¥
Must be non-combustible and at least
.018" thick (26 gauge)
¥
Must extend 6" to each side of the
appliance (measure from the side of the
firebox)
¥
Must extend 6" to the rear of the
appliance (measure from the stove top)
¥
Must extend 16" from the front
(measure from the faceplate)
¥
Minimum 38 1/4" deep by 33 3/8" wide
R
EQUIREMENTS
NFPA 211, listed wall shields, pipe shields, or other means approved by local
building or fire officials.
Minimum Clearance
(See the illustration below)
A
Sidewall to stove
B
Backwall to stove
C
Cornerwall to stove
D
Connector to sidewall
E
Connector to backwall
F
Connector to cornerwall
STRAIGHT
INSTALLATION
B
E
N O T E :
Clearances are measured from the stove top.
R
EQUIREMENTS
S
I
TOVE
Singlewall
Connector
18"
16 1/2"
10"
27"
19 1/2"
19 1/2"
CORNER
INSTALLATION
D
A
¥ AMERI-TEC model DCC with model HS chimney
¥ GSW model Super Chimney Twenty-One connected directly to appliance
¥ I.C.C. Excel 103HT Chimney with Ultrablack HP Double-Wall connector
6" Minimum
(from stove top)
16" Minimum
(from faceplate)
(C
NSTALLATION
Reduced
Clearance*
13"
9"
7 1/2"
21 1/2"
11 1/2"
16 1/2"
F
F
C
6" Minimum
(from the side
of the firebox)
Floor Protection
(Minimum .018" thick)
.)
ONT
P
7
AGE
C