Packing List; Floor Protection Requirements; Stove Placement Requirements - Lopi Answer Manual

Hide thumbs Also See for Answer:
Table of Contents

Advertisement

8
Stove Installation

Packing List

Wood Moisture Meter
Touch up paint
Gloves

Floor Protection Requirements

Stove must be placed on the Travis Industries legs.
Floor protection must extend to the sides, rear, and front of the stove (see "Clearances" for minimum
floor protection).
Floor protection must be non-combustible and at least .018" thick (26 guage).
No R value is required for floor protection - (R = 0).

Stove Placement Requirements

Clearances may be reduced by methods specified in NFPA 211, listed wall shields, pipe shields, or
other means approved by local building or fire officials.
Stove must be placed so that no combustibles are within, or can swing within (e.g. drapes, doors), 36"
(914mm) of the front of the stove
If the stove is placed in a location where the ceiling height is less than 7' (2134mm), it must follow the
requirements in the section "Alcove Installation Requirements"
Must maintain the clearances to combustibles (drywall, furniture, etc.) shown in following illustrations: