Table 5 Aux Mode Functions - Outback Power Systems FXR2012E Operator's Manual

Fxr series inverter/charger
Table of Contents

Advertisement

when energized. Diversion is usually used to regulate battery charging. The AC device is usually wired to
the output or load panel and must be left on. It must be sized to dissipate all energy from the renewable
source if necessary. Diversion will turn off following a delay when a low DC voltage setting is reached.
The AUX output will automatically turn on to run the loads if the inverter accepts an AC source.
Settable parameters include:
Low and high DC voltage
On and off delay
During variable conditions, the AUX output is triggered no more than once per minute (if voltage
conditions are still met). This prevents rapid nuisance cycling of the AC load.
AC Divert should not be used as the sole source of battery regulation. If the inverter shuts down or fails,
the batteries could suffer severe damage. This function should be supported by an external regulator.
If the inverter shuts down due to overload, the AUX output will also shut down. If the inverter
load exceeds 30 Aac, the AUX output will turn off to prevent an overload condition.
If either the FETs or the capacitors (see page 64) become too hot, the AUX will turn off due to
diminished inverter wattage capacity.
Note that even if every function in the menu is set to Off, external programming from other devices
may still activate the AUX output. An example is the system display's AGS function. See page 52.
The AUX functions are summarized in Table 5.
Name
Purpose
Load
Operates designated loads
normally; turns off loads in
Shed
severe conditions
Starts generator to charge
Gen Alert
batteries
Fault
Signals that the inverter shut
down due to error
Vent Fan
Runs fan to vent batteries
while charging
Runs fan to cool inverter
Cool Fan
DC Divert Turns on DC dump load to
prevent overcharging
GT Limits
Signals disconnect of grid-tied
inverter due to AC conditions
Source
Signals that the inverter
accepted an AC source
Status
AC Divert
Turns on AC dump load to
prevent overcharging
900-0169-01-00 Rev A
Table 5
Aux Mode Functions
Start
High Vdc
Low Vdc
Error present
High Vdc
Internal sensor > 60°C
High Vdc
GIP parameters
not met
AC source accepted
High Vdc
AC source accepted
Triggers
Stop
Low Vdc
High temp
Low output Vac
High input Aac
High Vdc
Error cleared
Below high Vdc
Internal sensor < 49°C
Low Vdc
GIP parameters met
AC source
disconnected
Low Vdc
High output load
High temperature
Operation
Settable
Points
Low & high Vdc
On & Off delay
Low & high Vdc
On & Off delay
None
High Vdc
Off delay
None
Low & high Vdc
On & Off delay
None
None
Low & high Vdc
On & Off delay
51