Defrost Control - Daikin FTKS20CVMB(9) Service Manual

Inverter pair wall mounted type c-series d-series
Hide thumbs Also See for FTKS20CVMB(9):
Table of Contents

Advertisement

SiENBE04-512A

3.10 Defrost Control

Outline
Heat Pump Only
Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor
heat exchanger temperature must be more than its fixed value when finishing.
Detail
Conditions for Starting Defrost
The starting conditions must be made with the outdoor air temperature and heat exchanger
temperature. Under the conditions that the system is in heating operation, 6 minutes after the
compressor is started and more than 28 minutes of accumulated time pass since the start of the
operation or ending the defrosting.
Conditions for Canceling Defrost
The judgment must be made with heat exchanger temperature. (4°C~22°C)
ARK(X)S models
(A)RK(X)H, R(Y)N models
Function and Control
Frequency
50sec.
ON
Compressor
OFF
ON
Four way valve
OFF
ON
Fan
OFF
450pps
Electronic expansion
valve opening
Frequency
55sec.
ON
Compressor
OFF
ON
Four way valve
OFF
ON
Fan
OFF
450pps
Electronic expansion
valve opening
0Hz
60sec.
600sec.
5sec.
350pps
0Hz
60sec.
480sec.
5sec.
450pps
Control Specification
PI control
50sec.
5sec.
450pps
Initial opening
(R4014)
PI control
45sec.
5sec.
450pps
Initial opening
(R4015)