Daikin FTKS20CVMB(9) Service Manual page 131

Inverter pair wall mounted type c-series d-series
Hide thumbs Also See for FTKS20CVMB(9):
Table of Contents

Advertisement

Troubleshooting
Troubleshooting
Check No.6
Refer to P.132
Check No.7
Refer to P.133
Check No.9
Refer to P.134
122
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Turn off the power and turn it on
again.
Error again or outdoor unit
fan activated?
NO
Check No.
9
Check the outdoor unit
fan or related.
Functioning
Radiation fin dirty?
Slightly dirty
Check No.
7
Check the installation condition.
: value for (A)RK(X)H, R(Y)N models
WARNING
To cool down the electricals, the
outdoor unit fan gets started when
the radiation fin temperature rises
above 80°C(85°C ) and stops itself
when it drops below 70°C(80°C ).
YES
Check No. 6
Check the thermistor resistance
value.
Fin thermistor
Check the radiation fin
temperature.
Thermistor as
specified in its characteristic
chart?
YES
Above
80°C(90°C
YES
Malfunctioning
Too dirty
SiENBE04-512A
NO
Replace the fin thermistor.
NO
Replace the outdoor unit
)?
PCB.
Replace the fan motor.
Correct the connectors and
fan motor leads.
Replace the outdoor unit
PCB.
Clean up the radiation fin.
Service Diagnosis
(R4016)