Target Discharge Pipe Temperature Control - Daikin FTKS20CVMB(9) Service Manual

Inverter pair wall mounted type c-series d-series
Hide thumbs Also See for FTKS20CVMB(9):
Table of Contents

Advertisement

Control Specification
3.11.7 Control when frequency is changed
When the target discharge pipe temperature control is active, if the target frequency is changed
for a specified value in a certain time period, cancel the target discharge pipe temperature
control and change the target opening of the electronic expansion valve according to the shift.

3.11.8 Target Discharge Pipe Temperature Control

Obtain the target discharge pipe temperature from the indoor and outdoor heat exchanger
temperature, and adjust the electronic expansion valve opening so that the actual discharge
pipe temperature become close to that temperature. (Indirect SH control using the discharge
pipe temperature)
Determine a correction value of the electronic expansion valve compensation and drive it
according to the deflection of the target discharge temperature and actual discharge
temperature, and the discharge temperature variation by the 20 sec.
60
Set the target discharge pipe
SC
temperature as to become an aiming
SH.
Regard that the inclination cannot be
changed due to the operating
SH
condition.
SiENBE04-512A
(R1389)
Function and Control

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents