Daikin FTKS20CVMB(9) Service Manual page 125

Inverter pair wall mounted type c-series d-series
Hide thumbs Also See for FTKS20CVMB(9):
Table of Contents

Advertisement

Troubleshooting
Troubleshooting
Check No.4
Refer to P.130
Check No.6
Refer to P.132
Check No.7
Refer to P.133
Check No.9
Refer to P.134
116
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Check the installation space.
Check No.7
Installation condition
check
Normal
Check No.9
Outdoor fan check
Normal
Check No.4
Electronic expansion valve check
Judgment
Normal
Check No.6
Heat exchanger thermistor check
Judgment
Normal
Abnormal
Abnormal
Abnormal
Abnormal
SiENBE04-512A
Change the air outlet grille
position.
Change the installation
location.
Clean the heat exchanger.
Replace the fan motor.
Repair the connector or fan
motor lead wires.
Replace the electronic
expansion valve or coil.
Replace the PCB.
Replace the heat exchanger
thermistor.
Replace PCB.
(R2855)
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents