Mains Supply - ESAB Warrior 500i CC/CV Instruction Manual

Hide thumbs Also See for Warrior 500i CC/CV:
Table of Contents

Advertisement

Available languages

Available languages

US
4.3

Mains supply

Mains supply requirements
High power equipment may, due to the primary current drawn from the mains supply, influence the
power quality of the grid. Therefore connection restrictions or requirements regarding the
maximum permissible mains impedance or the required minimum supply capacity at the interface
point to the public grid may apply for some types of equipment (see technical data). In this case it
is the responsibility of the installer or user of the equipment to ensure, by consultation with the
distribution network operator if necessary, that the equipment may be connected.
Make sure that the welding power source is connected to the correct supply voltage
and that it is protected by the correct fuse rating. Before connection and usage a
protective earth connection must be created in accordance with regulations.
Rating plate with supply connection data
Recommended fuse sizes and minimum cable area
Mains voltage
Mains cable area
Phase current I
eff
Fuse
anti-surge
type C MCB
Mains voltage
Mains cable area
Phase current I
eff
Fuse
anti-surge
type C MCB
NOTE!
The mains cable areas and fuse sizes as shown above are in accordance with Swedish
regulations. Use the power source in accordance with the relevant national regulations.
bu22a
Warrior 500i CC/CV
380V 3 50/60Hz
2
4C 8Awg / 4G 6mm
30A
35A
32A
Warrior 500i CC/CV
460V 3 50/60Hz
2
4C 8Awg / 4G 6mm
28A
35A
32A
- 10 -
440V 3 50/60Hz
2
4C 8Awg / 4G 6mm
28A
35A
32A
575V 3 50/60Hz
2
4C 8Awg / 4G 6mm
24A
25A
25A