Tranquility Console ® (TRC) Series Table of Contents Model Nomenclature: Tranquility® Console (TRC) Series (60Hz) Model Nomenclature: Tranquility® Console (TRC) Series (50Hz) General Information Unit Physical Data Installation Piping Connections - TRC Size 06-15 Piping Connections - TRC Size 18 Piping Connections Water-Loop Heat Pump Applications Ground-Loop Heat Pump Applications...
Page 2
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Consoles R e v. : 0 8 / 2 4 / 1 5 This Page Intentionally Left Blank C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s...
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Consoles R e v. : 0 8 / 2 4 / 1 5 General Information Safety CAUTION: Indicates a potentially hazardous situation or...
Page 6
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Consoles R e v. : 0 8 / 2 4 / 1 5 General Information Prepare units for installation as follows: Inspection - Upon receipt of the equipment, carefully...
400 psi [2758 kPa] are available for use manual to encourage thorough unit checkout at initial with ClimateMaster Console Units. Use the following start-up. These checklists are not a substitute for the guidelines when installing supply and return hose detailed information found in the Installation section assemblies.
Page 10
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Consoles R e v. : 0 8 / 2 4 / 1 5 Installation If the building drain connection is parallel with fl...
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Consoles R e v. : 0 8 / 2 4 / 1 5 Piping Connections - TRC Size 09-15 1.62 (41) 2.00...
Page 12
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Consoles R e v. : 0 8 / 2 4 / 1 5 Piping Connections - TRC Size 18 1.62 (41) 2.00...
fi nger-tight plus one quarter turn. Tighten steel fi ttings as necessary. Optional pressure-rated hose assemblies designed specifi cally for use with ClimateMaster units are available. Similar hoses can be obtained from alternate suppliers. Supply and return hoses are fi tted with swivel-joint fi ttings at one end to prevent kinking during installation.
[2.9 and 4.5 l/m per kW] of cooling capacity. room plumbing. In piping systems expected to utilize water ClimateMaster recommends 3 gpm per ton [3.9 l/m per temperatures below 50°F [10°C], 1/2” (13mm) closed cell kW] for most applications of water loop heat pumps. To...
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Consoles R e v. : 0 8 / 2 4 / 1 5 Ground-Loop Heat Pump Applications Antifreeze - If any liquid fl...
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Consoles R e v. : 0 8 / 2 4 / 1 5 Ground-Water Heat Pump Applications Use the appropriate scaling surface temperature for the Open Loop - Ground Water Systems - Shut off valves...
Page 17
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Consoles R e v. : 0 8 / 2 4 / 1 5 Ground-Water Heat Pump Applications Water Coil Low Temperature Limit Setting - For all Notice! Ground-water applications for commercial...
20 mesh] size. The ClimateMaster Water Quality Table provides water quality requirements for ClimateMaster coaxial heat exchangers. The water should be evaluated by an Rev.: 5/6/2014 S independent testing facility comparing to this Table and when properties are outside of these requirements, an external secondary heat exchanger must be used to isolate the heat pump heat exchanger from the unsuitable water.
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Consoles R e v. : 0 8 / 2 4 / 1 5 Electrical - Line Voltage General Line Voltage Wiring - Be sure the available WARNING!
Page 20
Model Voltage Motor Unit Circuit Fuse/ Unit Circuit Fuse/ Code Voltage Amps HACR Amps HACR 115/60/1 104-126 46.5 10.5 11.3 TRC09 208-230/60/1 197-254 23.0 265/60/1 239-292 19.0 115/60/1 104-126 50.0 10.0 12.4 11.5 13.8 TRC12 208-230/60/1 197-254 25.0 265/60/1 239-292 22.0...
Page 21
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Consoles R e v. : 0 8 / 2 4 / 1 5 Figure 3: Typical Field Installed Wiring WARNING! WARNING! To avoid possible injury or death due to electrical...
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Consoles R e v. : 0 8 / 2 4 / 1 5 Electrical - Low Voltage Unit-Mounted Control Models include digital display unit-mounted auto changeover (ACO) control.
Page 23
Thermostat installed low-voltage wiring is required. Compressor When desired, the unit can be furnished with a 24-volt control circuit which is fi eld-wired to a ClimateMaster- Reversing Valve supplied accessory remote thermostat. 24Vac Hot Low-voltage wiring between the unit and the wall...
R e v. : 0 8 / 2 4 / 1 5 TRC Series Wiring Diagram Matrix Diagrams can be lo cat ed online for 60 Hz go to www.climatemaster.com/commercial- wiring and for 50 Hz go to www.climatemaster.com/commercial-50Hz-wiring Wiring Diagram...
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Consoles R e v. : 0 8 / 2 4 / 1 5 CXM Controls CXM Control - For detailed control information, see DIP switch 1: Unit Performance Sentinel Disable -...
Note: This jumper should only be clipped Lockout Fast Flash Flashing fault code Closed under extenuating circumstances, as Test Mode recommended by ClimateMaster technical Night Setback Flashing Code 2 Flashing Code 3 services. Invalid T-stat Inputs Flashing Code 4 Not Clipped = 30°F [-1°C]. Clipped = 10°F...
Page 27
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Consoles R e v. : 0 8 / 2 4 / 1 5 On = Stage 1.
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Consoles R e v. : 0 8 / 2 4 / 1 5 Safety Features - CXM/DXM Controls Safety Features –...
Page 29
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Consoles R e v. : 0 8 / 2 4 / 1 5 If a UPS condition occurs, the control will immediate- CXM/DXM Control Start-up Operation - The control ly go to UPS warning.
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Consoles R e v. : 0 8 / 2 4 / 1 5 Unit Commissioning and Operating Conditions Environment - This unit is designed for indoor The commissioning table indicates air and water...
The manufacturer will not be responsible or liable appropriate. for damages from water leaks due to inadequate or 4. Verify that all strainers are in place (ClimateMaster lack of a pressurized leak test, or damages caused recommends a strainer with a #20 stainless steel wire by exceeding the maximum pressure rating during mesh).
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Consoles R e v. : 0 8 / 2 4 / 1 5 Unit and System Checkout Procedure SYSTEM CHECKOUT WARNING!
Check for vibration, noise, and water leaks. 5. Two factors determine the operating limits of 7. If unit fails to operate, perform troubleshooting ClimateMaster heat pumps, (a) return air temperature, analysis (see troubleshooting section). If the check and (b) water temperature. When any one of these...
• Cooling air and water values can vary greatly with and 80/67°F [27/19°C] in cooling; changes in humidity level. Table: 10 TRC Series Typical Operating Pressures and Temperatures (60 Hz I-P Units) TRC09 Full Load Cooling Full Load Heating Water...
Page 35
Table 11: Coax Water Pressure Drop Pressure Drop, PSI PD Added for Model GPM Motorized Water Valve 30°F 50°F 70°F 90°F TRC09 TRC12 TRC15 TRC18 c l i m a t e m a s t e r . c o m...
Allow unit to run 15 minutes in each mode before taking data. Do not connect service manifold gauges during start up unless instructed by ClimateMaster service tech. C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s...
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Consoles R e v. : 0 8 / 2 4 / 1 5 Preventive Maintenance Condensate Drain - In areas where airborne bacteria Water Coil Maintenance -...
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Consoles R e v. : 0 8 / 2 4 / 1 5 Functional Troubleshooting Fault Htg Clg Possible Cause...
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Consoles R e v. : 0 8 / 2 4 / 1 5 Performance Troubleshooting Performance Troubleshooting Htg Clg Possible Cause...
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Consoles R e v. : 0 8 / 2 4 / 1 5 Troubleshooting Form Look up pressure drop in I.O.M.
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Consoles R e v. : 0 8 / 2 4 / 1 5 Warranty (International) C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s...
Page 43
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Consoles R e v. : 0 8 / 2 4 / 1 5 Notes c l i m a t e m a s t e r .
ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specifi c information on the current design and specifi...
Need help?
Do you have a question about the TRC09 and is the answer not in the manual?
Questions and answers