ClimateMaster Tranquility 27 TT Series Installation Operation & Maintenance

ClimateMaster Tranquility 27 TT Series Installation Operation & Maintenance

Water-source heat pump system

Advertisement

Quick Links

Tranquility 27
Tranquility 20 (TS) Series
Tranquility 16 (TC) Series
Tranquility (TR) Series
Commercial
Horizontal & Vertical
Packaged Water-Source
Heat Pumps - 60 Hz
INSTALLATION, OPERATION
& MAINTENANCE
97B0075N01
Rev.: 03 January, 2011
(TT) Series
®

Table of Contents

Model Nomenclature - General Overview For
All H & V Series
General Information
Unit Physical Data
Electrical - Line Voltage
Typical Wiring Diagrams
Safety Features - CXM and DXM Controls
3
4
6
10
12
14
16
17
18
20
22
23
24
34
35
36
38
39
46
51
52
53
55
57
60
61
62
63
77
78
80
81
82
84

Advertisement

Table of Contents
loading

Summary of Contents for ClimateMaster Tranquility 27 TT Series

  • Page 1: Table Of Contents

    Tranquility 27 (TT) Series ® Tranquility 20 (TS) Series Tranquility 16 (TC) Series Table of Contents Tranquility (TR) Series Model Nomenclature - General Overview For All H & V Series General Information Unit Physical Data Horizontal Installation Field Conversion of Air Discharge Vertical Installation Piping Installation Water-Loop Heat Pump Applications...
  • Page 2 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 This Page Intentionally Left Blank C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s...
  • Page 3 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Model Nomenclature General Overview For All H &...
  • Page 4 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units Storage R e v. : 0 3 J a n u a r y, 2 0 1 1 Pre-Installation General Information Safety...
  • Page 5 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Pre-Installation - Installation, Operation, and �...
  • Page 6 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Unit Physical Data Tranquility 27 Two-Stage (TT) Series (60Hz Only)
  • Page 7 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Tranquility 20 Single-Stage (TS) Series (60Hz) Model Compressor (1 Each)
  • Page 8 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Tranquility 16 (TC) Series (60 Hz) TC Series Rotary...
  • Page 9 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Tranquility (TR) Series (60 Hz) TR Series Compressor (1 each)
  • Page 10 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Horizontal Installation Horizontal Unit Location Mounting Horizontal Units...
  • Page 11: Horizontal Installation

    UV based anti-bacterial systems may damage (e.g. louvered door). Therefore, filter rails are the industry coated air coils. standard and are included on ClimateMaster commercial heat pumps for the purposes of holding the filter only. For ducted return applications, the filter rail must be removed and replaced with a duct flange or filter rack.
  • Page 12: Field Conversion Of Air Discharge

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Field Conversion of Air Discharge Overview - Horizontal units can be field converted Figure 4: Left Return Side to Back...
  • Page 13 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units Condensate Piping R e v. : 0 3 J a n u a r y, 2 0 1 1 Duct System Installation Condensate Piping - Horizontal Units - Units are typi- Each unit must be installed with its own individual trap...
  • Page 14: Vertical Installation

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units Vertical Unit Location R e v. : 0 3 J a n u a r y, 2 0 1 1 Vertical Installation Vertical Unit Location - Units are not designed for Figure 7: Vertical Unit Mounting...
  • Page 15 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Sound Attenuation for Vertical Units - Sound Condensate Piping for Vertical Units - Vertical units attenuation is achieved by enclosing the unit within a...
  • Page 16: Piping Installation

    Optional pressure-rated hose assemblies designed Brass Fitting Rib Crimped Fitting specifically for use with ClimateMaster units are available. Similar hoses can be obtained from alternate suppliers. Supply and return hoses are fitted with swivel-joint fittings Length at one end to prevent kinking during installation.
  • Page 17: Water-Loop Heat Pump Applications

    Hose kits are available from ClimateMaster in different the tower and the water loop is recommended. If an configurations as shown in Figure 12 for connection open type cooling tower is used continuously, chemical between the unit and the piping system.
  • Page 18: Ground-Loop Heat Pump Applications

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Ground-Loop Heat Pump Applications Test individual horizontal loop circuits before backfilling.
  • Page 19 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Figure 13: Typical Ground-Loop Application Vibration Isolation Pad c l i m a t e m a s t e r .
  • Page 20: Ground-Water Heat Pump Applications

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Ground-Water Heat Pump Applications Open Loop - Ground Water Systems Open Loop - Ground Water Systems - Typical open...
  • Page 21 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Water Coil Low Temperature Limit Setting - For all open loop systems the 30°F [-1.1°C] FP1 setting (factory setting-water) should be used to avoid freeze damage to...
  • Page 22: Water Quality Standards

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Water Quality Standards Table 3: Water Quality Standards Water Quality...
  • Page 23: Electrical - Line Voltage

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Electrical - Line Voltage Electrical - Line Voltage - All field installed wiring, in- �...
  • Page 24 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Electrical - Line Voltage Table 4a: Tranquility 27 (TT) Series Electrical Data (Standard Units)
  • Page 25 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Table 4c: Tranquility 20 (TS) Series Electrical Data - (PSC Motor &...
  • Page 26 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Table 4d: Tranquility 20 (TS) Series Electrical Data - (PSC High Static Motor &...
  • Page 27 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Table 4e: Tranquility 20 (TS) Series Electrical Data - (ECM Motor &...
  • Page 28 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Table 4f: Tranquility 20 (TS) Series Electrical Data - (PSC Motor &...
  • Page 29 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Table 4g: Tranquility 20 (TS) Series Electrical Data - (PSC High Static Motor &...
  • Page 30 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Table 4h: Tranquility 20 (TS) Series Electrical Data - (ECM Motor &...
  • Page 31 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Table 4j: Tranquility (TR/TC) Series Electrical Data - (Standard 60Hz Units) Voltage Total...
  • Page 32 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Table 4k: Tranquility TR Series Electrical Data with Secondary Pump- (Standard 60Hz Units) Voltage Total...
  • Page 33 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Table 4l: Tranquility TR Series High Static Electrical Data with Secondary Pump- (Standard 60Hz Units) Voltage Total...
  • Page 34: Electrical - Power Wiring

    Figure 17. Most ClimateMaster units are shipped on the medium speed tap. Consult submittal data or engineering design guide for specific unit airflow tables. Typical unit design delivers rated airflow at nominal static (0.15 in.
  • Page 35: Electrical - Power & Low Voltage Wiring

    10°F [-12.2°C] refrigerant temperature, a more suitable Fan Motor temperature when using an antifreeze solution. All ClimateMaster units operating with entering water temperatures below 59°F [15°C] must include the ELECTRICAL - LOW VOLTAGE WIRING optional water/refrigerant circuit insulation package to prevent internal condensation.
  • Page 36: Electrical - Low Voltage Wiring

    Taco “A” is designed to control accessory devices, such as 500 series (ClimateMaster P/N AVM) and Taco SBV water valves. Note: This terminal should be used only series valves. Slow closing valves take approximately with 24 Volt signals and not line voltage.
  • Page 37 The field installed high pressure switch shall have a cut-out pressure of 300 psig and a cut-in pressure of 250 psig. This pressure switch can be ordered from ClimateMaster with a 1/4” internal flare connection as part number 39B0005N02. Taco Valve...
  • Page 38: Electrical - Thermostat Wiring

    IOM and or unit wiring diagram. Practically temperature measurement. Position the thermostat any heat pump thermostat will work with ClimateMaster back plate against the wall so that it appears level and units, provided it has the correct number of heating and so the thermostat wires protrude through the middle cooling stages.
  • Page 39: Blower Performance Data

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Blower Performance Data TT Standard Unit - No Reheat Residential...
  • Page 40 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 TS Blower Performance Data (ECM Motor) - Standard Unit - No Reheat Residential...
  • Page 41 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 TS Blower Performance Data Standard Unit - No Reheat (PSC Motor) Airflow in CFM with wet coil and clean air filter...
  • Page 42 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 TS Blower Performance Data Units With ClimaDry (PSC Motor) TSH/V/D with Reheat ESP Loss...
  • Page 43 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 TC Blower Performance Data Airflow in CFM with wet coil and clean air filter Airflow (cfm) at External Static Pressure (in.
  • Page 44 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 TR Blower Performance Data Standard Unit Airflow (cfm) at External Static Pressure (in.
  • Page 45 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 TR Blower Performance Data High Static Airflow (cfm) at External Static Pressure (in.
  • Page 46: Ecm Blower Control

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 ECM Blower Control The ECM fan is controlled by an interface board that CFM Adjust Settings: The CFM adjust setting allows...
  • Page 47 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 The ramp down feature may be eliminated during an ESD (Emergency Shut Down) situation when using a DXM unit controller.
  • Page 48 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Typical Wiring Diagram - Units with CXM Board and ECM Fan Motor (Single Phase) C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s...
  • Page 49 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Typical Wiring Diagram - Units with CXM Board and PSC Fan Motor (Single Phase) c l i m a t e m a s t e r .
  • Page 50 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Typical Wiring Diagram - Units with DXM Board and PSC Fan Motor (Three Phase) C l i m a t e M a s t e r Wa t e r - S o u r c e H e a t P u m p s...
  • Page 51 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Typical Wiring Diagram - Units with CXM Board, ECM Fan Motor, and MPC (DDC) CONTROLS (SINGLE PHASE) c l i m a t e m a s t e r .
  • Page 52: Cxm Controls

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 CXM Controls CXM Control - For detailed control information, see DIP switch 2: Stage 2 Selection - provides selection of...
  • Page 53: Dxm Controls

    25 sec) under extenuating circumstances, as DXM is non-functional Open Fault Retry Slow Flash Flashing fault code Open recommended by ClimateMaster technical Lockout Fast Flash Flashing fault code Closed services. Test Mode Not Clipped = 30°F [-1°C]. Clipped = 10°F...
  • Page 54 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 1.3 - Thermostat type (heat pump or heat/cool): DIP 1.3 DIP Package #2 (S2) - DIP Package #2 has 8 switches provides selection of thermostat type.
  • Page 55 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Safety Features CXM and DXM Controls Safety Features –...
  • Page 56 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 If a UPS condition occurs, the control will immediately CXM/DXM Control Start-up Operation go to UPS warning.
  • Page 57: Climadry Modulating Reheat Option

    The cooling/heating modes are like any other the unit will continue to run in 1st Stage Heating ClimateMaster WSHP. The reversing valve (“O” signal) until the call is removed or satisfied, shutting down is energized in cooling, along with the compressor the unit.
  • Page 58 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Since dehumidification is generally only required in ClimaDry Application Considerations - Unlike most cooling, most ground loop systems will not experience...
  • Page 59 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Table 7: Humidistat/Dehumidistat Logic &...
  • Page 60: Unit Starting And Operating Conditions

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Unit Starting and Operating Conditions Commissioning Conditions Consult Table 9b for the particular model.
  • Page 61: Piping System Cleaning And Flushing

    4. Verify that all strainers are in place (ClimateMaster access to all connections is limited. Test pressure may recommends a strainer with a #20 stainless steel not exceed the maximum allowable pressure for the wire mesh).
  • Page 62: Unit And System Checkout

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Unit and System Checkout �...
  • Page 63: Unit Start-Up Procedure

    5. Two factors determine the operating limits d. Refer to table 17. Check the temperature of both of ClimateMaster heat pumps, (a) return air entering and leaving water. If temperature is within temperature, and (b) water temperature. When any range, proceed with the test.
  • Page 64 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Figure 28: Test Mode Pins �...
  • Page 65 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Table 10b: TS Coax Water Pressure Drop *Note: To convert Pressure Drop, psi [kPa]*...
  • Page 66 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Table 10c: TC Coax Water Pressure Drop Pressure Drop, psi [kPa]* U.S.
  • Page 67 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Operating Pressure/Temperature Tables Include the Following Notes: •...
  • Page 68 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Table 11: TT Series Typical Unit Operating Pressures and Temperatures: Continued TT049 Full Load Cooling - without HWG active...
  • Page 69 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Table 12: TS Series Typical Unit Operating Pressures and Temperatures (60Hz - I-P Units) TS006 Full Load Cooling...
  • Page 70 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Table 12: TS Series Typical Unit Operating Pressures and Temperatures: Continued TS018 Full Load Cooling - without HWG active...
  • Page 71 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Table 12: TS Series Typical Unit Operating Pressures and Temperatures: Continued TS036 Full Load Heating - without HWG active...
  • Page 72 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Table 12: TS Series Typical Unit Operating Pressures and Temperatures: Continued TS060 Full Load Cooling - without HWG active...
  • Page 73 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Table 13: TR/TC Series Typical Unit Operating Pressures and Temperatures TR/TC006 Full Load Cooling - without HWG active...
  • Page 74 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Table 13: TR/TC Series Typical Unit Operating Pressures and Temperatures: Continued TR/TC015 Full Load Cooling - without HWG active...
  • Page 75 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Table 13: TR/TC Series Typical Unit Operating Pressures and Temperatures: Continued TR/TC030 Full Load Cooling - without HWG active...
  • Page 76 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Table 13: TR/TC Series Typical Unit Operating Pressures and Temperatures: Continued TR/TC048 Full Load Cooling - without HWG active...
  • Page 77: Preventive Maintenance

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Preventive Maintenance Water Coil Maintenance - (Direct ground water especially important to provide consistent washing of...
  • Page 78: Functional Troubleshooting

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Functional Troubleshooting Fault Htg Clg Possible Cause...
  • Page 79 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Thermostat wiring Check G wiring at heat pump.
  • Page 80: Start-Up Log Sheet

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Start-Up Log Sheet Installer: Complete unit and system checkout and follow unit start-up procedures in the IOM.
  • Page 81: Functional Troubleshooting

    Location: ________________________ Model Number: ________________________ T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Serial Number: ________________________ Date: ________________________ Packaged Units...
  • Page 82: Warranty (U.s. & Canada)

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Warranty (U.S.
  • Page 83 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Packaged Units R e v. : 0 3 J a n u a r y, 2 0 1 1 Notes: c l i m a t e m a s t e r .
  • Page 84: Revision History

    97B0075N01 ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.

Table of Contents