Storage; Unit Clearances - Trane TC*150-301 Installation Operation & Maintenance

Packaged electric/electric 12 ½ - 25 ton
Table of Contents

Advertisement

General Information
Request an immediate joint inspection of the damage by the carrier and the consignee. Do not
remove damaged material from the receiving location.
Take photos of the damage, if possible. The owner must provide reasonable evidence that the
damage did not occur after delivery.
Notify the appropriate sales representative before installing or repairing a damaged unit.
Fiberglass Wool
Product contains fiberglass wool. Disturbing the insulation in this product during installation,
maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic
fibers known to the state of California to cause cancer through inhalation. Glass wool fibers may
also cause respiratory, skin or eye irritation.
Precautionary Measures
First Aid Measures

Storage

Take precautions to prevent condensate from forming inside the unit's electrical compartments and
motors if:
Note: Do not use the unit's heater for temporary heat without first completing the start-up
The manufacturer will not assume any responsibility for equipment damage resulting from
condensate accumulation on the unit's electrical and/or mechanical components.

Unit Clearances

Figure 1, p. 13
multiple unit installation. These clearances are the minimum distances necessary to assure
adequate serviceability, cataloged unit capacity, and peak operating efficiency.
Providing less than the recommended clearances may result in condenser coil starvation, "short-
circuiting" of exhaust and economizer airflows, or recirculation of hot condenser air.
12
WARNING
Avoid breathing fiberglass dust.
Use a NIOSH approved dust/mist respirator.
Avoid contact with the skin or eyes. Wear long-sleeved, loose-fitting clothing, gloves, and eye
protection.
Wash clothes separately from other clothing: rinse washer thoroughly.
Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations
requiring additional respiratory protection. Use the appropriate NIOSH approved respiration
in these situations.
Eye Contact - Flush eyes with water to remove dust. If symptoms persist, seek medical
attention.
Skin Contact - Wash affected areas gently with soap and warm water after handling.
the unit is stored before it is installed; or,
the unit is set on the roof curb, and temporary heat is provided in the building. Isolate all side
panel service entrances and base pan openings (e.g., conduit holes, S/A and R/A openings, and
flue openings) from the ambient air until the unit is ready for start-up.
procedure detailed under "Starting the Unit" .
illustrates the minimum operating and service clearances for either a single or
RT-SVX25C-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents