3. Do not run the electrical wires transporting DC signals in or around conduit housing high
Table 4.
Distance from Unit
to Control
0 - 150 feet
0 - 45.7 m
151 - 240 feet
46 - 73.1 m
241 -385 feet
73.5 - 117.3 m
386 - 610 feet
117.7 - 185.9
611 - 970 feet
186.2 - 295.7
Figure 13. Reliatel refrigeration module
RT-SVX25C-EN
voltage wires.
Zone sensor module wiring
Recommended Wire
Size
22 gauge
.33 mm2
20 gauge
.50 mm2
18 gauge
.75 mm2
16 gauge
m 1.3 mm2
14 gauge
m 2.0 mm2