R410a split system - wall unit heat pump - up to 16.9 seer 9,000 - 18,000 btu/hr (30 pages)
Summary of Contents for Trane TRAE050 1C
Page 1
Cond. Unit TRAE - 5 to 30 TR (Axial Fan) Cond. Unit CRCB - 5 to 15 TR Cond. Unit CRCE - 5 to 15 TR Split System 50/60Hz Models: TRAE050 1C TRCE050 1C CRCB050 1C CRCE050 1C TRAE200 1C TRAE075 1C...
Page 2
Important: As Trane do Brasil has the policy of continually enhancing its products, it reserves the right to change specifications and drawings without prior notice. Only techni- cians accredited and/or authorized by Trane should install and maintain equipment specified in this manual.
Contents I-General Data II-Unit Inspection III-Transport and Movement IV-Refrigeration Piping (Interconnection) V-Maintenance VI-Operational and Electric Features VII-Wiring Diagram VIII-Dimensional Data Aplication Considerations TRAE/TRCE IX-Standard Conversion Table SSC-SVN008E-EN...
I-General Data TRAE/TRCE Tab I-01 - General Data - Condensing Units TRAE - 050 to 300 M o del 10 0 12 5 15 0 20 0 2 5 0 3 0 0 N ominal Cap. To n 1 2,5 D im e nsi o ns Width 1 1 40...
Page 5
General Data CRCB/CRCE Tab. I-03 - General Data - Condensing Unit CRCE 050 to 150 for use w/ SIVE. Model 12,5 Nominal Cap. 1491 1712 1712 Length 1217 Depth Height 1393 1494 1545 1620 1849 Coil Rows FPF (Fins per foot) 0,99 1,39 1,72...
- Report damages and actions to be - Perform the hydraulic installation should perform installation, startup and taken for appropriate repair to Trane do required to drain water from the maintenance in this equipment. Brasil and/or the Contractor. The unit condensate drip pan.
III-Transport and Movement Fig. III-01 - Instructions for transport and movement. Instructions for handling 4. Do not remove module package until WA RNIN G! its placement in the permanent and movement installation location. Be careful when To avoid death or unit damage, moving the equipment.
11 /8" 2 1/8" 11/8" 2 5/8" condenser units. Note: For equivale nt lengths above the values indicated, please contact Trane or an authorized installer. - Carry out refrigerant charge. MOUNTING DIAGRAM MOUNTING DIAGRAM DRIER FILTER DRIER FILTER AND LIQUID SIGHT GLASS...
Page 9
18 m. SUCTION distances higher than recommended value, please contact LIQUID Trane do Brasil. Evaporating Unit above Condensing Unit - Build a 20 cm inverted syphon in the suction line at the evaporating unit outlet, after the regular oil accumulation Fig.
Page 10
15,30 + 15,30 8,00 + 8,00 each kg of refrigerant added due to tubing. Tab. IV-05 - Additional load of refrigerant R-407. Suction Line Note: The oil used and the Trane Oil 48 Diameter Liquid Line (kg/m) (kg/m) (R-407 - Synthetic). 1/2”...
Page 11
Refrigerating Tubing - Interconnection CRCB/CRCE Recommendations for refrigerating b. In the horizontal sections of the and accessories installation discharge line, put a 45 mm inclination in the direction of the flow of refrigerant Condenser Unit above Evaporator each 10 meters. Unit a.
V-Periodic Preventive Maintenance Preventive Maintenance Check the liquid line sight glass. Annual Maintenance Test against leakages and repair them, if Perform recommended IMPORTANT required. quarterly and monthly maintenance If operational conditions and l i quid services. Perform all inspections and mainte- sight glass indicate lack of gas, Ask a qualified technician to nance services at recommended...
Page 13
Corrective Maintenance Compressor Installation Evacuation this case, cleaning should proceed as The compressor may have problems - Evacuation is required to remove water follows: mainly at two levels: mechanical or steam and non-condensable gases from 2.1. Collect all refrigerant in a cylinder electric.
IX-Standard Conversion Table To convert fr om: To : Multiply B y: To convert fro m: T o: Mu ltipl y By: Le ngth Vel ocity Fe et (ft) meters (m) 0,30481 Feet per min ute (ft/min) meter s pe r se con d (m/s) 0 ,0 0508 Inche ( in) milimeters (mm)