Trane TC*150-301 Installation Operation & Maintenance page 53

Packaged electric/electric 12 ½ - 25 ton
Table of Contents

Advertisement

Note: Measurements should be made from LED common (ZSM terminal 6 to respective LED
Table 12. System mode and fan selection
Resistance Valves
(Ohms)
2.32K
4.87K
7.68K
10.77K
13.32K
16.13K
19.48K
27.93K
35.0K
43.45K
Out of Range(Short)
Out of Range (Open)
Programmable & Digital Zone Sensor Test
Testing serial communication voltage
1. Verify 24 VAC is present between terminals J6-14 & J6-11.
2. Disconnect wires from J6-11 and J6- 12. Measure the voltage between J6-11 and J6-12, should
3. Reconnect wires to terminals J6-11 and J6-12. Measure voltage again between J6-11 and J6-12,
4. Verify all modes of operation, by running the unit through all of the steps in the "Test Modes"
5. After verifying proper unit operation, exit the test mode. Turn the fan on continuously at the
ReliaTel Refrigeration Module (RTRM) Default Chart
If the RTCI loses input from the buildingmanagement system, the RTRM will control in the default
mode after approximately 15 minutes. If the RTRM loses the Heating and Cooling setpoint input,
the RTRM will control in the default mode instantaneously.
The temperature sensing thermistor in the Zone Sensor Module is the only component required
for the "Default Mode" to operate.
Unit Operation without a Zone Sensor
This procedure is for temporary operation only. The economizer and condenser fan cycling
functions are disabled.
1. Open and Lock the unit disconnect switch.
2. Remove the Outside Air Sensor (OAS) from the condenser section of unit.
3. Use two (2) wire nuts, to individually cap the wires.
RT-SVX25C-EN
terminal). Refer to the Zone Sensor Module (ZSM) Terminal Identification table at the
beginning of this section.
Zone Sensor Unit/
Fan Mode
Off/ Auto
Cool/Auto
Auto/Auto
Off/On
Cool/On
Auto/On
Heat/Auto
Heat/On
Emergency Heat/Auto Emergency Heat
Emergency Heat/On
INVALID/Short
INVALID/Open
be about 32 VDC.
voltage should flash high and low every 0.5 seconds. The voltage on the low end will measure
about 19 VDC, while the voltage on the high end will measure from approximately 24 to 38 VDC.
section discussed in "Unit Start-Up" .
ZSM, by pressingthe button with the fan symbol. If the fan comes on and runs continuously,
the ZSM is good. If you are not able to turn the fan on, the ZSM is defective.
Local Unit Mode
Local Fan Mode
Off
Auto
Cool
Auto
Auto
Auto
Off
On
Cool
On
Auto
On
Heat
Auto
Heat
On
Auto
Emergency Heat
On
Invalid (CV), Auto (VAV) Invalid
Invalid (CV), Off (VAV)
Invalid
Troubleshooting
53