Electromechanical Thermostat 24V Ac Conductors With Reliatel - Trane TC*150-301 Installation Operation & Maintenance

Packaged electric/electric 12 ½ - 25 ton
Table of Contents

Advertisement

Installation
Note: All field wiring must conform to NEC guidelines as well as state and local codes.
Control Power Transformer
The 24 volt control power transformers are to be used only with the accessories called out in this
manual. Transformers rated greater than 50 VA are equipped with internal circuit breakers. If a
circuit breaker trips, turn "Off" all power to the unit before attempting to reset it.
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable
frequency drives or other energy storing components refer to the appropriate manufacturer's
literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate
voltmeter that all capacitors have discharged. Failure to disconnect power and discharge
capacitors before servicing could result in death or serious injury.
The transformer is located in the control panel. The circuit breaker is located on the left side of the
transformer and can be reset by pressing in on the black reset button.
Controls using 24 VAC
Before installing any connecting wiring, refer to
access locations provided on the unit and
1. Use copper conductors unless otherwise specified.
2. Ensure that the AC control wiring between the controls and the unit's termination point does
Note: Resistance in excess of 3 ohms per conductor may cause component failure due to
3. Be sure to check all loads and conductors for grounds, shorts, and mis-wiring.
4. Do not run the AC low voltage wiring in the same conduit with the high voltage power wiring.
5. Route low voltage wiring per illustrations on the next page.
Table 3.
Distance from Unit to
Control
000 - 460 feet
000 - 140 m
461 - 732 feet
Controls using DC Analog Input/Outputs (Standard Low Voltage Multiconductor Wire)
Before installing any connecting wiring between the unit and components utilizing a DC analog
input\output signal, refer to
provided on the unit.
1.
Note: Resistance in excess of 2.5 ohms per conductor can cause deviations in the accuracy of the
2. Ensure that the wiring between controls and the unit's termination point does not exceed two
26
WARNING
not exceed three (3) ohms/conductor for the length of the run.
insufficient AC voltage supply.

Electromechanical thermostat 24V AC conductors with Reliatel

Recommended Wire
Size
18 gauge
.75 mm2
16 gauge
Table 4, p. 27
lists the conductor sizing guidelines that must be followed when interconnecting
the DC binary output devices and the system components utilizing a DC analog input\output
signal to the unit.
controls.
and a half (2.5) ohms/ conductor for the length of the run.
Figure 2, p. 14
Table 3, p. 26
Figure 2, p. 14
and
Figure 4, p. 15
and
Figure 4, p. 15
for AC conductor sizing guidelines, and;
for the electrical access locations
for the electrical
RT-SVX25C-EN