DSC MAXSYS PC4020 Installation Manual page 25

Hide thumbs Also See for MAXSYS PC4020:
Table of Contents

Advertisement

Command Output X (X=1-8) (13-20)
This function key provides the user with a simple
method for activating a PGM Output programmed as
Command Output option #1-8 (see Section 11.4 "PGM
Output Options"). Once this key is pressed, the user may
need to enter a valid access code if the Cmd.Out X Rq Cd
option is enabled for the command output.
Silence Trouble (21)
Pressing this key silences trouble beeps for the partition.
If the Trouble Requires Code system toggle option is
enabled, the user will be required to enter an access code
in order for this function key to work (see section 7.4
"Access Code Options").
Silence Bells (22)
Pressing this key followed by entry of a valid access code
will silence the partition's fire alarms.
Fire Reset (23)
Pressing this key followed by entry of a valid access code
will restore all fire alarms.
S e c t i o n
6 :
K e y p a d
Fire Drill (24)
Pressing this key followed by entry of a valid access or
Master code will initiate the Fire Drill. This is the equiva-
lent of entering [ ][6][Access/Master Code][5].
Lamp Test (25)
Pressing this key followed by entry of a valid access or
Master code will initiate the Lamp Test. This is the equiv-
alent of entering [ ][6][Access/Master Code][8] (see
Instruction Manual, section 5.3 "Lamp Test").
Fire Insp Tst (26)
Pressing this key followed by the Walk Test Code will
initiate the Fire Inspector's Test Mode. This is the equiva-
lent of entering [ ][6][Walk Test Code][4]. If the test
mode is already active, pressing this key followed by the
Walk Test Code will disable the test ([ ][6][Walk Test
Code][5]).