Master/Slave Connections - Viking R-6 Installation Instructions And Use & Care Manual

Vehicular gate operator
Table of Contents

Advertisement

ELECTRICAL INSTALLATION – MASTER/SLAVE
ELECTRICAL INSTALLATION – MASTER/SLAVE

Master/Slave Connections

Master Unit
Caution – Do not run Master/Slave communication cable in
the same conduit as the power supply (120-220V) cable.
Use 18 AWG stranded wire
with foil overshield and drain
wire or better.
Guard Station
Master/Slave
The control board provides a connector for master/slave connectivity. This
connector will allow synchronized operation with a second gate operator.
Wire the operators as shown above and interconnect the two operators as follows:
Master Board
GND . . . . . . . . . . . . . . . . . . . .GND
Close . . . . . . . . . . . . . . . . . . .Close
Stop . . . . . . . . . . . . . . . . . . . .Stop
Open . . . . . . . . . . . . . . . . . . .Open
Shield (to Earth)
For Overlap Delay see page 28.
Outside
Interconnecting
Conduit
UL
Siren
Slave Board
Shield (to Earth)
Note: It is recommended to connect all external
devices and set timer and overlap delay control
on the master unit. Ensure Slave Control Board
has timer set to 'OFF' to allow the Master to
control the timer.
TECHNICAL SUPPORT 1 800 908 0884
Opens First
Inside
Conduit
Guard Station
Slave Unit
Shielded Cable
NOTE:
Use 16 Gauge
Wire for runs
up to 100'
Shield Wire
UL
Siren
Master/Slave
Purpose
Reference
Close Command
Stop Command
Open Command
19