Tranquility Digital (DXM2) ® Troubleshooting Guide DIGITAL Geothermal Heat Pumps TE/TZ/TES/TEP 97B0601N01 Rev.: 3/10/15 Table of Contents Introduction Verifying DC Voltage on DXM2 Board for Modulating Valve Check Troubleshooting Flow Chart TXV Bulb Test Flow Chart Reference Symbols and Diagrams Verifying Dipswitch Position Contactor Chart Replacing High Pressure Water Switch...
Set up and diagnostics are made easier using the communicating thermostat (ATC32) or the communicating service tool (ACDU02). You must have ATC32 or ACDU02 to properly work on ClimateMaster Tranquility Digital units that use the DXM2 ®...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Troubleshooting Flow Chart If it is still not Verify that...
Page 4
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Troubleshooting Flow Chart Continued Replace...
Page 5
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Troubleshooting Flow Chart Continued Verify that...
Page 6
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Troubleshooting Flow Chart Continued Check your...
Page 7
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Troubleshooting Flow Chart Continued Unit does...
Page 8
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Troubleshooting Flow Chart Continued The unit...
Page 9
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Troubleshooting Flow Chart Continued Verify the Water Side...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Notes: Specific to Splits When using TES/TEP with communicating Air Handlers (and not using ATC32U02 Thermostat using a 24 volt...
Page 11
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Reference Symbols and Diagrams for Flow Chart w w w.
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Contactor Chart Contactor Chart Motor does...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Removing Powerhead on ¾-Inch Modulating Valve On 3/4”...
Page 14
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Removing Powerhead on 1-Inch Modulating Valve Rotate dial to ‘1’...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Checking Compressors Compressor Ohms Table Compressor...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 An Alternative Way of Checking Compressors Megohm Values of Copeland Compressors There are many factors that affect megohm readings...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Reversing Valve Touch Test Chart Suction Line to Compressor...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Performance Troubleshooting Symptom Htg Clg Possible Cause...
Page 19
Check for dirty air filter and clean or replace Low Suction Reduced air flow Check fan motor operation and airflow restrictions Pressure in cooling Too high of external static - check static vs blower table Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ®...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Functional Troubleshooting Fault Htg Clg Possible Cause...
Page 21
Air temperature out of range LT2 Fault - Code 5 design parameters that IOM specifies. Low Air Temperature Improper low temperature setting Normal airside applications will require. Only setting for (30°F vs 10°F) packaged units is 30º. Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ®...
Page 22
Check fan motor operation and airflow restrictions Low Air Coil or ClimaDry Too high of external static - check static vs blower table Pressure Fault Too much cold vent air - bring entering air temp within (ClimaDry) Code 11 Air temperature out of range design parameters Tranquility D i g i t a l ( D X M 2 ) —...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Typical Split Water-to-Air Troubleshooting Form Split Water-to-Air RP930...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Typical Water Source Refrigeration Circuit (Heating Cycle) Water-to-Water (Heating Only) RP932...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Unit Operating Conditions TZ Coax Water Pressure Drop TE Coax Water Pressure Drop...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Basic Refrigeration Summary Expansion Valve System •...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Refrigeration Troubleshooting Measuring Superheat and Subcooling Superheat and subcooling are a good indication of refrigeration efficiency.
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Refrigeration Troubleshooting Superheat = Suction Line Temperature - Suction Saturation Temperature...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Auxiliary Heat Check 24 volts DC First stage auxiliary heat...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Compressor Contactor Voltage Check 18-31.5 Volts AC...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Verifying Capacitor First, remove the power to the unit and allow 5-10 minutes for the capacitor to...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Replacing Variable-Speed Pump Power Head 1) You can remove power head from motor with # 25 Torx driver if feedback is out of range.
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Verifying Antifreeze Place hydrometer in antifreeze.
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Second Stage Verification Remove When rectifier is...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Verifying 24V at Reversing Valve Verify 24V at reversing valve when calling for cooling To check the solenoid’s magnetic pull, begin by pulling solenoid off of reversing valve.
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 A0-2 Jumper For Mod Valve For Pump...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Verifying DC Voltage on DXM2 Board for Modulating Valve Check A-X 1 2 3 4 5 6 7 8...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 TXV Bulb Test Pressure Gauge Suction pressure increases when...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Verifying Dipswitch Position 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Verifying a Thermistor Clamp on digital to read ref next to LT1 to verify sensor Remove this Molex plug to check resistance of the FP1/...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Verifying a Thermistor Thermistor Temperature Sensors –...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Turning Breaker on in Panel or Auxiliary Heat Control 197 - 254 V...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Locating Thermostat Version and DXM2 Version INSTALLER SETTINGS THERMOSTAT CONFIG...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Checking Dipswitches on DXM2 Verify that dipswitch number 1 is in the ‘On’...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Checking Blower Line Voltage Note: Be sure to turn power off...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Hard Reset of Thermostat Use a thermostat wire to connect TP2 and TP3 on the thermostat board.
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Units Having LT1 Lockouts In Heating with Modulating Valve (Open Loop) B-L When running unit in Y1 and Y2, if valve position moves slightly below 50% open, there is a greater impact on GPM.
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Electrical—Power Wiring 9-15V DC 9-15V DC...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 LT2 Sensor Location for Non-TAH Air Handlers Do not install LT2 sensor...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Definitions of Conditions CONTACTOR OPEN - NOT BUZZING replace overload if it is located in the electrical box.
Page 52
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Definitions of Conditions MOTOR WINDINGS OVERHEATED When the compressor is drawing normal amps and becomes...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 DXM2 Board Layout and Dipswitches Water Coil Low Temp...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 AXM Board Layout and Dipswitches Condensate Sensor...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 DXM2 Controls FIELD SELECTABLE INPUTS JUMPERS (Set at Factory)
Page 56
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 DXM2 Controls On = Normal Fan Mode.
Page 57
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 DXM2 Controls Fault Code 3: Loss of Charge Switch –...
Page 58
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 DXM2 Controls Fault Code 8: Unit Performance Sentinel –...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Typical Wiring Diagram—96B0005N55 w w w.
Page 60
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 DXM2 Wiring Diagram with Internal Flow Controller - 96B0005N60 This diagram includes typical wiring details but is not applicable to all units.
Page 61
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 DXM2 Wiring Diagram with Motorized Modulating Water Valve - 96B0005N62 This diagram includes typical wiring details but is not applicable to all units.
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 ATC32U02 Thermostat Screens and Set Up 2.0 Installer Menu Settings 2.2.1...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 ATC32U02 Thermostat Screens and Set Up 3.0 System Configuration AIRFLOW SELECTION...
Page 64
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 ATC32U02 Thermostat Screens and Set Up �...
Page 65
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 ATC32U02 Thermostat Screens and Set Up VARIABLE SPD INTERNAL PUMP CONFIGURATION...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 ATC32U02 Thermostat Screens and Set Up 9.0 Service Mode CONTROL DIAGNOSTICS...
Page 67
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 ATC32U02 Thermostat Screens and Set Up DIPSWITCH CONFIGURATION FAULT HISTORY...
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 ATC32U02 Thermostat Screens and Set Up 9.4.2 Flow Conditions 9.4.5 Possible Causes...
Page 69
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 Notes: w w w.
Page 70
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 G e o t h e r m a l H e a t i n g a n d C o o l i n g...
Page 71
Tranquility D i g i t a l ( D X M 2 ) — Tr o u b l e s h o o t i n g G u i d e ® R e v. : 1 0 M a r c h , 2 0 1 5 w w w.
97B0601N01 ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.