ClimateMaster Tranquility 20 TSD 006 Series Installation Operation & Maintenance

ClimateMaster Tranquility 20 TSD 006 Series Installation Operation & Maintenance

60hz - hfc-410a

Advertisement

Tranquility
(TS) Series
Models TSD/H/V 006 - 070
60Hz - HFC-410A
INSTALLATION, OPERATION
& MAINTENANCE
97B0075N06
Revised: 17 June, 2015
20
®
®
®
®
3
4
6
7
9
10
11
13
14
15
17
19
20
26
27
28
29
30
31
32
33
35
36
39
40
42
44
47
49
50
52
®
52
57
58
59
60
61
62
63
64

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Tranquility 20 TSD 006 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for ClimateMaster Tranquility 20 TSD 006 Series

  • Page 1: Table Of Contents

    Tranquility ® (TS) Series Model Nomenclature - General Overview General Information Unit Physical Data Horizontal Installation Field Conversion of Air Discharge Horizontal Installation Vertical Installation Piping Installation Water-Loop Heat Pump Applications Ground-Loop Heat Pump Applications Ground-Water Heat Pump Applications Water Quality Standards Electrical - Line Voltage Electrical - Power Wiring Electrical - Power &...
  • Page 2 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 3: Model Nomenclature - General Overview

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 4: General Information

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 5 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 6: Unit Physical Data

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 7: Horizontal Installation

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 8 (e.g. louvered door). Therefore, fi lter rails are the industry coated air coils. standard and are included on ClimateMaster commercial heat pumps for the purposes of holding the fi lter only. For ducted return applications, the fi lter rail must be removed and replaced with a duct fl...
  • Page 9: Field Conversion Of Air Discharge

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 10: Horizontal Installation

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 11: Vertical Installation

    (e.g. louvered door). Therefore, fi lter rails are the industry standard and are included on ClimateMaster commercial heat pumps for the purposes of holding the fi lter only. For ducted return applications, the fi lter rail must be removed and replaced with a duct fl...
  • Page 12 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 13: Piping Installation

    Compressor vibration may Optional pressure-rated hose assemblies designed be transmitted through the hoses to the structure, specifi cally for use with ClimateMaster units are available. causing unnecessary noise complaints. Similar hoses can be obtained from alternate suppliers. Supply and return hoses are fi tted with swivel-joint fi ttings at one end to prevent kinking during installation.
  • Page 14: Water-Loop Heat Pump Applications

    Hose kits are available from ClimateMaster in different treatment and fi ltering will be necessary. confi gurations as shown in Figure 12 for connection between the unit and the piping system.
  • Page 15: Ground-Loop Heat Pump Applications

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 16 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 17: Ground-Water Heat Pump Applications

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 18 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 19: Water Quality Standards

    20 mesh] size. The ClimateMaster Water Quality Table provides water quality requirements for ClimateMaster coaxial heat exchangers. The water should be evaluated by an Rev.: 5/6/2014 S independent testing facility comparing to this Table and when properties are outside of these requirements, an external secondary heat exchanger must be used to isolate the heat pump heat exchanger from the unsuitable water.
  • Page 20: Electrical - Line Voltage

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 21: Ts) Series

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 22: Ts) Series

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 23: Ts) Series

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 24: Ts) Series

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 25 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 26: Electrical - Power Wiring

    Figure National Electrical Code as well as all applicable local 16. Most ClimateMaster units are shipped on the medium codes. Refer to the unit electrical data for fuse sizes. speed tap. Consult submittal data or engineering design Consult wiring diagram for fi...
  • Page 27: Electrical - Power & Low Voltage Wiring

    Figure 18 to change the setting to 10°F [-12.2°C] refrigerant temperature, a more suitable temperature when using an antifreeze solution. All ClimateMaster units operating with entering water temperatures below 60°F [15.6°C] must include the optional water/refrigerant circuit insulation package to Low voltage prevent internal condensation.
  • Page 28: Electrical - Low Voltage Wiring

    Figure 19 shows typical wiring for a 24VAC external solenoid valve. Figures 20 and 21 illustrate typical slow closing water control valve wiring for Taco 500 series (ClimateMaster P/N AVM) and Taco SBV JW3-LT1 jumper series valves. Slow closing valves take approximately should be 60 seconds to open (very little water will fl...
  • Page 29: Electrical - Thermostat Wiring

    IOM and or unit wiring diagram. Practically back plate against the wall so that it appears level and any heat pump thermostat will work with ClimateMaster so the thermostat wires protrude through the middle units, provided it has the correct number of heating and cooling stages.
  • Page 30: Ts Blower Performance Data - (Ecm Motor) - Standard Unit - No Reheat

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 31: Ts Blower Performance Data - Standard Unit - No Reheat (Psc Motor)

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 32: Ts Blower Performance Data - Units With Climadry ® (Psc Motor)

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 33: Ecm Blower Control

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 34 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 35: Typical Wiring Diagram - Units With Cxm Board And Ecm Fan Motor (Single Phase)

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 36: Typical Wiring Diagram - Units With Cxm Board And Psc Fan Motor (Single Phase)

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 37 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 38 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 39: Cxm Controls

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 40: Dxm Controls

    Description of Alarm Relay Operation (green) (yellow) (red) circumstances, as recommended by ClimateMaster technical services. Normal mode Open Cycle (closed 5 sec, Not Clipped = 30°F [-1°C]. Clipped = 10°F Normal mode with UPS Flashing Code 8 open 25 sec) [-12°C].
  • Page 41 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 42: Safety Features - Cxm And Dxm Controls

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 43 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 44: Climadry ® Modulating Reheat Option

    The cooling/heating modes are like any other the unit. NOTE: Not all units have two-stage heating ClimateMaster WSHP. The reversing valve (“O” signal) functionality. is energized in cooling, along with the compressor •...
  • Page 45 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 46 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 47: Piping System Cleaning And Flushing

    fi lling the system, for ClimaDry ® to operate properly. 4. Verify that all strainers are in place (ClimateMaster Note: The manufacturer strongly recommends all recommends a strainer with a #20 stainless steel wire piping connections, both internal and external to the mesh).
  • Page 48 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 49: Unit And System Checkout

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 50: Unit Start-Up Procedure

    If temperature is within 5. Two factors determine the operating limits range, proceed with the test. If temperature is of ClimateMaster heat pumps, (a) return air outside of the operating range, check refrigerant temperature, and (b) water temperature. When any pressures and compare to table 11.
  • Page 51 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 52: Unit Operating Conditions

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 53 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 54 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 55 T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 56 C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 57: Preventive Maintenance

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 58: Functional Troubleshooting

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 59: Performance Troubleshooting

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 60: Start-Up Log Sheet

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 61: Functional Troubleshooting

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 62: Warranty (U.s. & Canada)

    C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S ® Tr a n q u i l i t y 2 0 ( T S ) S e r i e s R e v.
  • Page 63: Warranty (International)

    T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y ®...
  • Page 64: Revision History

    ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specifi c information on the current design and specifi...

Table of Contents