Chapter 5: Communication Interface

NOTE:
The UPS can still function properly without making the connections below.
RS232 port (9-pin female connector) is built into the UPS rear panel. You can use the provided RS232
cable to connect the UPS with a computer and use the included CD to install the SMART2000 software
to check and monitor the UPS status via a computer.
z
RS232 port provides the following functions:
1. Monitor UPS status:
Load level, battery status, battery voltage, UPS mode, input voltage, input frequency, out-
put voltage, and unit inside temperature
2. Set shut-down delay time
3. Enable/ disable beep
4. Remote shut-down
z
Pin Assignment:
1. PIN 2: TXD <Transmitting Data>
2. PIN 3: RXD <Receiving Data>
3. PIN 5: GND <Signal Ground>
z
Hardware:
1. Baud Rate ....... 2400bps
2. Data Length ......8 bit
3. Stop Bit ............1 bit
4. Parity ...............None
NOTE:
Ú You can also download the software from the link, http://59.125.232.140.
Ú Before you use the RS232 port, please make sure that you have removed a mini-size card from
the SMART slot. Do not use RS232 port and SMART slot at the same time.
This interface is for connection to a facility's Remote Emergency Power Off (REPO) circuit. When the
UPS is connected to the REPO circuit, it enables emergency shutdown of the UPS and the UPS has
no output. Connect this remote control port to a user-supplied normally-closed or normally-open switch.
Please refer to Figure 5-a.
Figure 5-a: Use a screwdriver to push the area shown by the two black arrows to open the Remote Con-
trol Port, and connect the port to a user-supplied normally-closed or normally-open switch.

RS232 Port

Remote Control Port