Delta Amplon RT 5kVA Installation & Operation Quick Manual

Advertisement

Quick Links

Delta UPS - Amplon Family
Delta External Charger Box for
Amplon RT 5/ 6/ 8/ 10/ 15/ 20kVA UPS
Installation & Operation Quick Guide
ENGLISH
5013296801
1
Product Introduction
The Delta External Charger Box works as an external charger for a 5~20kVA
on-line UPS. Its output power factor reaches to 0.97 and efficiency is up to
90%. The charger box provides wide range of charge voltage (120Vdc to
290Vdc) for you to adjust according to battery capacity. Working with a UPS,
the charger box can charge lead-acid batteries and lithium batteries. Through
the provided RJ45 cable, the charger box can send alarm signals to the UPS,
which enhances the UPS's monitor function.
CH1
CH2
NORMAL
NORMAL
CHARGER
(Figure 1: Delta External Charger Box Front View)
2
Important Safety Instructions
Please read this user manual before operation and keep it for later reference.
Failure to heed the manual will void the warranty.
y
Install the charger box in a well-ventilated area. Do not expose it to rain,
dust, and moisture. Keep it away from flammable gas or explosives.
y
To protect the charger box from overheating and to ensure its reliability,
do not block or cover its slits and openings.
y
Do not put beverages on the charger box.
y
All maintenance services must be performed by qualified personnel. Do
not open or remove the cover of the charger box to avoid high voltage
electric shock.
y
The charger box must be well grounded due to a possible risk of current
leakage.
y
There is a risk of dangerous high voltage when the batteries are still
connected to the charger box. Before maintenance of the charger box,
do not forget to remove the input power cord and disconnect the battery
cable to completely cut off the power source.
y
Standard Compliance
CE and cTUVus (UL 62368-1)
FCC Class A
EN 61000-4-2, Level 4
EN 61000-4-6
EN 61000-4-3, Level 3
EN 61000-4-4, Level 4
EN 61000-4-5, 2kV (Common mode)
www.deltaww.com
3
3
Package List
Usage Warnings & Symbols
1
CH1
CH2
NORMAL
NORMAL
CHARGER
2
3
4
× 4
× 2
× 4
× 4
6
7
× 2
× 1
No.
Item
1
Delta External Charger Box
2
Installation & Operation Quick Guide
3
Ear kit
4
Tower Stand Extender
5
Terminal CU
6
Bus bar for DC output
7
Micro USB cable
8
RJ45 Cable
4
LED Indicators
1
2
CH1
CH2
NORMAL
NORMAL
CHARGER
3
4
(Figure 2: LED Indicators)
1 / 4
LED No.
1
2
5
× 8
3
× 4
8
4
× 1
Q'ty
5
Rear Panel
1 PC
1 PC
1 SET
4 PCS
8 PCS
2 PCS
1 PC
1 PC
No. Printing
1
RS 485
MICRO
2
USB
3
ID
DC
4
OUTOPUT
5
AC INPUT
Continue to the Next Page
LED Status
Meaning
Off
CH1 works normally.
Flashing (Red)
CH1's setting is abnormal.
On (Red)
CH1 works abnormally.
Off
CH2 works normally.
Flashing (Red)
CH2's setting is abnormal.
On (Red)
CH2 works abnormally.
Off
CH1's input power is abnormal.
Flashing (Green)
CH1's input power is out of working range.
On (Green)
CH1's input power is normal.
Off
CH2's input power is abnormal.
Flashing (Green)
CH2's input power is out of working range.
On (Green)
CH2's input power is normal.
CH2
CH1
RS485
ID
ID
RS485
MICRO
USB
DC OUTPUT
CH2
CH1
1
3
1 2
4
(Figure 3: Rear Panel)
Meaning
Description
For connection to the RS485 port on
UPS.
With a UPS, you can detect charger box
RS 485
information and control the charging
voltage to synchronize with the UPS.
RS 485 and Micro-USB can not be
communicated at the same time.
Micro-USB
For configuring the charger box's
port
setting.
You can set communication ID by DIP
DIP Switch
Switch, please refer to Table 1 for ID
setting.
Output
For connection to battery cabinet.
terminal
Input
For connection to power input.
terminal

AC INPUT
L (L1)
N (L2)
5

Advertisement

Table of Contents
loading

Summary of Contents for Delta Amplon RT 5kVA

  • Page 1 On (Green) CH1's input power is normal. CH2's input power is abnormal. The Delta External Charger Box works as an external charger for a 5~20kVA on-line UPS. Its output power factor reaches to 0.97 and efficiency is up to Flashing (Green) CH2's input power is out of working range.
  • Page 2: Installation And Configuration

    (Figure 5: Install the Delta External Charger Box on Your Rack) ID22 ID22 NOTE: 90° ID23 ID23 If you want to use a non-Delta rail kit, please only follow step ID24 ID24 ID25 ID25 Tower Mounting: Connect the provided tower stand extenders with the tower stands...
  • Page 3: Troubleshooting

    Connect the Delta external charger box to UPS Troubleshooting Before installing input cables and output cables, fix the bus bar (provided in packing) first. See Figure 10 . Problems Solutions Charge RT 15-20kVA UPS Charge RT 5-10kVA UPS Indicators Check whether the...
  • Page 4: Technical Specifications

    0 ~ 95% (non-condensing) Humidity NOTE: 1. * At a distance of 3.28 ft (1 meter) in front of the Delta external charger box. 2. * De-rate to 75% load when the operating temperature is over 40°C (104°F), de-rate to 50% load when the operating temperature is over 50°C (122°F).
  • Page 5: Micro Usb

    UPS - Amplon 台达 系列 包装清单 序号 状态 说明 灭掉 充电板工作正常。 台达外接充电箱 闪烁(红) 充电板参数设定不正常。 Amplon RT 5/ 6/ 8/ 10/ 15/ 20kVA UPS 适用于 亮灯(红) 充电板工作不正常。 安装操作指南 NORMAL NORMAL 灭掉 充电板工作正常。 CHARGER 闪烁(红) 充电板参数设定不正常。 简体中文 亮灯(红) 充电板工作不正常。 × 4 × 8 灭掉...
  • Page 6 表 :通讯 设定 & 按照步骤 到 将充电箱安装到台达的固定导轨上(选配)。如 图 拉出台达充电箱的控制面板( ),顺时针旋转 °( ) 并 。 重新插入控制面板 ( ) 。 之后, 将台达铭牌顺时针旋转如 ° ( ) 。 通讯指拨开关 如 图 。 步骤 :根据机架调整固定导轨的长度。 CH2 ID CH1 ID 设定 设定 步骤 :旋紧固定导轨的螺帽。 DIP1 DIP2 DIP3 DIP4 DIP5...
  • Page 7 连接台达外接充电箱和 输入 输出线的规格,请参考下表: 故障排除 在安装充电箱输入和输出线材前,先将附件中的铜排依下图位置固 定。如 图 。 CHG240-RT-1/ CHG240-RT-2 规格 灯号颜色 输入 输出线 说明 故障排除方法 #12AWG (3 mm 状态 连接RT 15-20kVA UPS 连接RT 5-10kVA UPS 额定温度 ° 闪烁 5.07kgf-cm (4.40 lb-in) 充电板设定不正常。 紧力扭矩 请确认充电板设定是否正确。 红色 DC OUTPUT AC INPUT DC OUTPUT AC INPUT 如以上条件皆已排除,请联系经销...
  • Page 8 1600W 3200W 輸出 功率 Delta Electronics (Americas) Ltd. Delta Energy Systems Australia Pty Ltd. 46101 Fremont Blvd. Fremont, CA 94538 Unit 20-21, 45 Normanby Road, Notting Hill VIC 3168, Australia T +1 510 344 2157 T +61 3 9543 3720...