ALLIANCE UW50P4 Installation & Maintenance page 16

Pocket hardmount we-4, we-5 control
Table of Contents

Advertisement

Installation
NOTES:
1. 208/240 3 Phase 4 Wire Standard
2. 208/240 3 Phase 3 Wire Optional
3. 440/480 3 Phase 3 Wire Optional
4. 380/415 3 Phase 4 Wire Optional
Provide 3 phase circuit breakers.
Electrical connections are made to the J-Box.
Machine Net Weight = 1250 lbs.
USE ALL FLEXIBLE CONNECTIONS ONLY!
Information subject to change without notice.
Machine must be properly grounded.
Installation shall conform with local codes and/or the
National Electrical Code.
Do not use fuses.
Plumbing Specs
Minimum Drain Size = 3 inches
Minimum supply size = 3/4 inch
Hot and Cold
Minimum Water Pressure = 40 psi
Maximum Stream Pressure = 120 psi
Drain lines must be vented.
Average Gals./Cycle = 110
Provide 30 Amp circuit breaker disconnect for
208/240 3 phase machine.
14
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
White
Red
TO CONTROL
MODULE
Blue
Black
1
J-BOX MOUNTED ON REAR OF CONTROL MODULE
1
Ground Lug
Ground
Figure 6
Electrical connections are made at the J-Box located
on the rear of the control module. The machine must
be connected to the electrical supply shown on the
identification plate attached to the side of the control
module.
For personal safety and proper operation, the machine
must be grounded as per state and local codes. In the
absence of these codes, grounding must conform with
National Electric Code article 250-95. The ground
connection may be to a proven earth ground at the
location service panel and/or to a grounded metal cold
water pipe.
Do not connect the ground to the neutral (N
wire) leg at the terminal strip. If the machine is
intended for 4 wire service, a neutral leg must be
provided by the power company. Do not connect the
neutral leg to the ground lug.
If a Delta Supply System is used, the high leg must be
connected to the red wire (L3) at the terminal strip. If
three-phase service is not available and a Roto-Phase
or other phase adder is used, the artificial leg must be
connected to the red wire (L3).
Improper connections will result in equipment damage
and will void the warranty. It is your responsibility to
have all electrical connections made by a properly
licensed and competent electrician to assure that the
electrical installation is adequate. Improper
installation will result in voiding the warranty.
N
T (L3)
S (L2)
R (L1)
PHM185N
Connect to Proven Earth
white
F232160

Advertisement

Table of Contents
loading

Table of Contents