Manual Call Points Special Design - Honeywell ESSER FACP Technical Information

Table of Contents

Advertisement

Periphery components for ESSER FACP
6.6

Manual Call Points special design

6.6.1 Standard MCP Ex (i) and IQ8MCP Ex (i) for use in Ex areas
Conventional and addressable manual call points for use in Ex areas. These manual call points with "intrinsic
safety" ignition protection are operated over esserbus
alternatively as a spur - exclusively IQ8MCP Ex (i) - directly with Ex barrier (Part No 804744) on the loop of the
ESSER fire alarm control panels.
General detector data according to ATEX
Max. Input voltage (Ui)
Max. Input current (Ii)
Max. Output current (Io)
Max. internal Capacity (Ci)
Ambient temperature (Ta)
Examination
Certificate No.
Category
Ex-protection
Specification
Detector identification according to ATEX
Fig. 26: Identification example
Fig. 27: Example identification plate IQ8MCP Ex (i)
40
Standard MCP Ex (i)
804920.EX
804960.EX
:
:
:
:
:
:
TÜV 14 ATEX 150860
:
II 2G (with Ex barrier Part No. 764744 / 804744)
:
EN 60079-0:2012 +
:
A11:2013/ -11:2012
IQ8MCP Ex (i)
®
transponders and Ex barrier (Part No. 764744) or
21 V DC
252 mA
---
---
- 20 °C ... + 70 °C
Ex ib IIC T4 Gb
Fig. 28: EC-Type Examination acc.
Construction Products Regulation (CPR)
IQ8MCP Ex (i)
804924.EX
804961.EX
10 mA
1 nF
TÜV 14 ATEX 150789
EN 60079-0:2012 +
A11:2013/ -11:2012/ -25:2010
TI 798960.GB0 / 04.20