12.
EXTERNAL INPUT & OUTPUT

EXTERNAL INPUT

Indoor unit type
Control input
Compact
Cassette
Slim Duct
Wall Mounted
Floor / Ceiling
Floor
12-1.
EXTERNAL INPUT
CONTROL INPUT (Operation/Stop or Forced stop)
Compact
Cassette
Connector
CN102
The air conditioner can be remotely operated by means of the following on-site work.
"Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit.
Unit operation is started at the following contents by adding the contact input of a commercial ON/OFF switch to a
connector on the external control PC board and turning it ON.
Unit operation
Operation mode
Set temperature
Airflow mode
Air direction (swing)
z
Circuit diagram example
Indoor unit
control PC board *1
Connector
1
3
*1 PC board of Communication kit is used for Wall mounted type (LJ, LU, LM).
*2 Make the distance from the PC board to the connected unit within 10m.
Contact capacity: DC 24 V or more, 10 mA or more.
Indoor unit type
Compact Cassette
Slim Duct
Wall Mounted
Floor / Ceiling
Floor
Operation status
Fresh air control
output
Wall Mounted
Slim Duct
LJ
CN102
CN303
Initial setting after power is ON
Auto changeover
24°C
AUTO
Standard air direction (swing OFF)
Connected unit
Ex.) Switch
10 m *2
Signal
Field supply
1 Pin
(Polarity)
-
-
LJ
+
LU
-
LM
-
LF
-
-
-
- (01-141) -
EXTERNAL OUTPUT
Auxiliary heater
output
output
-
-
-
-
-
-
-
Floor / Ceiling
LU / LM
LF
CNA01
CN14
Starting mode other than initial setting
Mode at previous operation
Temperature at previous operation
Mode at previous operation
Air direction at previous operation
3 Pin
(Polarity)
+
+
-
+
+
+
+
+
Error status output
-
-
(LU / LM types)
-
-
Floor
CN102
CN14