Outdoor Unit (3 Rooms Type); Specifications - Fujitsu AU*G07LVLA Technical Manual

Multi : 2rooms type 3rooms type 4rooms type
Hide thumbs Also See for AU*G07LVLA:
Table of Contents

Advertisement

1.

SPECIFICATIONS

The following performance is a value at standard combinations.
STANDARD COMBINATION
AO  G18LAT3 : AS  G07LMCA + AS  G07LMCA + AS  G07LMCA
AO  G24LAT3 : AS  G07LMCA + AS  G07LMCA + AS  G09LMCA
Type
Model name
Power source
Available voltage range
Cooling
Capacity
Heating
Cooling
Input power
Heating
Cooling
Current
Heating
EER
Cooling
COP
Heating
Starting current
Maximum operating current
Cooling
Airflow rate
Heating
Fan
Type x Q'ty
Motor output
Cooling
Sound pressure level *1
Heating
Dimension (H × W × D)
Fin pitch
Heat
exchanger
Rows x Stages
type
Pipe type
Fin type
Type x Q'ty
Compressor
Motor output
Type (Global Warming Potential)
Refrigerant
Charge
Refrigerant oil
Type
Material
Enclosure
Colour
Net
Dimensions
H ×W ×D
Gross
Net
Weight
Gross
Size
Method
Pre-charge length (Total)
Max. length (Total)
Max. length (Each)
Connection pipe
Min. length (Total)
Min. length (Each)
Max. height difference between
Outdoor Unit and each Indoor Units.
Max. height difference between
Indoor Units.
Cooling
Operation range
Heating
NOTE:
Specifications are based on the following conditions.
Cooling: Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB / 24 °CWB.
Heating: Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB / 6 °CWB.
Pipe length: 5 m, Height difference: 0 m. (Outdoor unit - indoor unit)
The protective function might work when using it outside the operation range.
*1: These are the measured values in the manufacturer's anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified
values here.
*2: Connect to connection valve by the adapter
kW
Rated
Btu/h
kW
Min. - Max.
Btu/h
kW
Rated
Btu/h
kW
Min. - Max.
Btu/h
Rated
Max.
kW
Rated
Max.
Rated
A
Rated
kW/kW
A
A
3
m
/h
W
dB(A)
mm
W
g
mm
kg
Liquid
mm
Gas
m
°C
- (03 - 01) -
INVERTER MULTI MODELS
HEAT PUMP TYPE
AOG18LAT3
AOG24LAT3
230V ~ 50Hz
198-264V ~ 50Hz
5.4
18400
1.8 - 6.8
6100 - 23200
6100 - 29000
6.8
23200
2.0 - 8.0
6800 - 27300
6800 - 31400
1.35
2.06
1.62
2.06
5.9
7.1
4.00
4.20
7.1
9.0
3050
2750
Propeller × 1
100
46
47
672 × 900 × 36.4
1.45
2 × 32
Copper tube
Aluminium
DC TWIN ROTARY × 1
1100
R410A (1975)
2200
POE
Steel sheet
BEIGE
(Approximate colour of MUNSELL 10YR7.5 / 1.0NN)
700 × 900 × 330
835 × 1050 × 445
55
63
Ø6.35 (Ø1/4 in.) × 3
Ø9.52 (Ø3/8 in.) × 2, [Ø12.70 (Ø1/2 in.) × 1]
Flare
30
50
25
15
5
15
10
-10 to 46
-15 to 24
6.8
23200
1.8 - 8.5
8.0
27300
2.0 - 9.2
1.94
2.60
2.00
2.87
8.5
8.8
3.51
4.00
8.8
12.5
3300
3300
48
49
2