Faraday MPC-6000 Programming Manual page 27

Fire alarm system control unit
Table of Contents

Advertisement

Below are the different parameters that may be set for each of the different devices:
FireSmart
Smoke
Detector
Parameter
8713
Label
X
Application
X
Sensitivity
When app
off
ROR
-
Led off
X
Pre-alarm
When app
off
Verification
When app
off
Alarm
X
Waterflow
-
Sil. Waterflow
-
Trouble
-
Supervisory
X
Non-fire
-
Panel reset
-
Alarm silence
-
Acknowledge
-
Test
-
Manual Pull
-
*Available only for first input usage.
NOTE: When programming requires yes or no, press 1 for YES and 0 for NO.
The following table provides a description of the parameters that may be set for each
device.
Parameter
Label
Each device may have a forty character label assigned to it to describe the input. This label
will be displayed when the input becomes active.
Application
The FireSmart detectors have internal algorithms that may be set for different environments.
A setting of "none" turns off the algorithms and allows the detector sensitivity to be set
manually and verification to be selected.
Sensitivity
This sets the level of smoke that will cause the device to generate an alarm. This is only
appropriate for smoke detectors.
ROR
Rate of rise thermal alarm. This is used for the FireSmart detector and the thermal detector
when the temperature rises at a rate of xx degrees/minute.
Led off
Used to disable the LED on the device so that it does not indicate polling. It will still flash red
for alarm.
Pre-alarm
Selected when an early warning of a fire alarm is required.
Verification
This is selected to cause the device to go through the UL defined verification cycle to
eliminate false alarms.
M P C
Thermal
Photo
Detector
Smoke
station
Detector
8712
8710
8700-S
8700-D
8700-M
X
X
-
-
-
X
X
-
X
X
-
X
-
X
X
X
-
-
-
-
-
-
-
X
-
-
-
-
-
-
-
-
-
-
-
-
23
6 0 0 0 / 7 0 0 0
P R O G R A M M I N G
Loop Devices
Pull
Single
Dual
input
input
monitor
monitor
module
module
8701
8703
8702
X
X
X
-
-
-
-
-
-
-
X
X
-
-
-
-
X
X
X
-
X
X
-
X
X
-
X
X
-
X
X
-
X
X
-
X
X
-
X
X
-
X
X
-
X
X*
-
-
Description
M A N U A L
Single
Conven-
input
tional
monitor
Zone
module
module
with relay
8704
8705
X
X
-
-
-
-
-
-
-
-
-
X
X
-
-
-
-
-
X
X
X
X
X
X
X
X
-
X
X
X
-
X
-
X
-
X
-
X
-
-
-
X
LED
output
8726
X
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-