M P C
6 0 0 0 / 7 0 0 0

QUICK START

Automatic programming of a new system

This is the quickest way to get a system operational. After all of the devices,
notification appliances and option modules have been programmed and installed,
check all wiring for grounds, shorts and opens. Connect SLUs, SRUs, NACs and
any other field wiring to the panel.
Automatic programming is selected from the Technician Level. Below are the steps
to access the Technician Level.
Step
Action
1
Press "Menu" and then press "More" until
the option "Tech. Level" is displayed.
2
Press "Tech. Level".
3
Enter the password on the keypad. The
default is "0 1 2 3 4 5".
4
Press "Enter" or "D".
Once the Technician Level has been accessed, following are the steps to activate
the autoprogram function.
Step
Action
1
Select "Edit" by pressing "4".
2
Select "Autoprgm" by pressing "7".
3
Start the autoprogram by pressing the "D"
key.
P R O G R A M M I N G
M A N U A L
Description
The display will show the entry
screen for the technician level
access password.
The password will appear in the
screen.
The display will show the starting
screen of the Technician Level.
Description
The display will show the first
screen of the Edit functions with
"Auto Pgm" as one of the options.
The display will show the
Autoprgm screen.
The display will show all of the
addresses being checked as the
auto program is performed. This
could take several minutes. As
each new device is found, the
display will allow the installer to
chose whether to include the found
device. When the autoprogram is
finished, the screen will return to
the Edit options.
6