Termination Locations; Vent Termination Minimum Clearances - Heat & Glo SL350TRSI-N-CE Owner's Manual

Heat & glo sl350trsi-n-ce; sl350trsi-pb-ce fireplace
Hide thumbs Also See for SL350TRSI-N-CE:
Table of Contents

Advertisement

6 6

Termination Locations

A. Vent Termination Minimum Clearances
Fire Risk.
Maintain vent clearance to combustibles as
specifi ed.
• DO NOT pack air space with insulation or other
materials.
Failure to keep insulation or other materials away
from vent pipe may cause overheating and fi re.
61 cm MIN.
TERMINATION
CAP
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
Angle
0°-26.6°
.......................................................... 30*
26.6°-30.3° .......................................................... 38*
30.3°-33.7° .......................................................... 46*
33.7°-36.9° .......................................................... 61*
36.9°-39.8° .......................................................... 76*
39.8°-42.5° .......................................................... 99
42.5°-45.0° ........................................................ 1 22
45.0°-49.4° ........................................................ 1 52
49.4°-53.1° ........................................................ 1 83
53.1°-56.3° ........................................................ 2 13
56.3°-59.0° ........................................................ 2 29
59.0°-60.3° ........................................................ 2 44
*.91 M minimum in snow regions
Figure 6.1 Minimum Height From Roof To Lowest Discharge
Opening
24
WARNING
HORIZONTAL
OVERHANG
51 cm MIN.
VERTICAL
WALL
LOWEST
DISCHARGE
OPENING
X
30,5 cm
ROOF PITCH
IS X/ 30,5 cm
H (Min.) cm
Heat & Glo • SL350TRSI-N-CE, SL350TRSI-PB-CE • 2033-980 Rev. L • 3/14
A
15,2 cm (minimum) up to 50,8 cm
50,8 cm and over
Gas, Wood or Fuel Oil
Termination Cap
B
Gas
Termination
Cap **
* If using decorative cap cover(s), this distance may need to be
increased. Refer to the installation instructions supplied with the
decorative cap cover.
** In a staggered installation with both gas and wood or fuel oil
terminations, the wood or fuel oil termination cap must be higher
than the gas termination cap.
Figure 6.2 Staggered Termination Caps