Liebert GXTTM User Manual page 28

6 & 10 kva 230v
Table of Contents

Advertisement

MODEL NUMBER
MODEL RATING VA/W (max)
DIMENSIONS: mm (in)
Unit
W x D x H
Shipping
W x D x H
WEIGHT: kg (lbs)
Unit
Shipping
Input/Output Connections
INPUT AC PARAMETERS
Voltage Range (typical)
100% - 90% Loading
90% - 70% Loading
70% - 30% Loading
30% - 0% Loading
Frequency
OUTPUT AC PARAMETERS
Voltage
Frequency
Waveform
Main Mode Overload
BATTERY PARAMETERS
Type
Qty. x Voltage x Rating
Back-up Time
Recharge Time
(Internal Batteries Only)
ENVIROMENTAL
Operating Temperature
Storage Temperature
Relative Humidity
Operating Elevation
Storage Elevation
Audible Noise
AGENCY
Safety
EMI/EMC
Immunity
SPECIFICATIONS
GXT6000T-230X
6000 / 4200
260 x 555 x 803
(10.5 x 22.0 x 31.5)
400 x 850 x 1065
(16.0 x 33.5 x 42.0)
139 (306)
170 (374)
Hardwire terminal block
230 VAC nominal; variable based upon output load
186 VAC to 280 VAC; ±5.0 VAC
159 VAC to 280 VAC; ±5.0 VAC
139 VAC to 280 VAC; ±5.0 VAC
119 VAC to 280 VAC; ±5.0 VAC
46.6 – 52.4 Hz or 57.1 - 62.9 Hz; auto sensing
208/220/230/240 VAC (switch selectable); ±7%
50 Hz or 60 Hz; auto sensing
200% for 8 cycles; 130% for 10 seconds with transfer to
Valve-regulated, nonspillable, lead acid
20 x 12V x 7.0 Ah
7 min. minimum
7 hours to 95% capacity after full discharge into 100%
0° C to +40° C (+32° F to +104° F)
-15° C to +50° C (+5° F to +122 °F)
0% to 95%, non-condensing
Up to 3000 m (10,000 ft.) at 40° C without derating
15.000 m (50,000 ft.) maximum
<55 dB "A" at 1 metre
EN50091-1-1; TUV/GS Listed; CE Low Voltage Directive
EN50091-2, Class A; CE EMC Directive
IEC 801-2, Level 4 / IEC 801-3,
Level 3 / IEC 801-4, Level 4 / IEC801-5,Level 3
26
GXT10000T-230X
10000 / 7000
340 x 650 x 960
(13.5 x 25.5 x 38.0)
510 x 840 x 1235
(20.0 x 33.0 x 48.5)
244 (538)
284 (626)
Sinewave
bypass
40 x 12V x 7.0 Ah
10 min. minimum
load
<65 dB "A" at 1 metre