Liebert GXTTM User Manual page 22

6 & 10 kva 230v
Table of Contents

Advertisement

Stabilisers/Levelling Feet
When the UPS is located in its final position before or after wiring, it is necessary
to fit stabiliser brackets and, if necessary, adjust the levelling feet. If the UPS is
wired using a rigid wiring system, then movement of the UPS must be prevented
by winding down the 4 levelling feet under the UPS as shown below. For UPS
wired with flexible cables, this is optional. Note- Access to the levelling feet is
obstructed by the stabiliser brackets, on the GXT10000 models.
Adjust the levelling feet as necessary using a 12mm open ended
spanner/wrench. DO NOT LOOSEN THE LARGER NUT ABOVE, AS THIS
FIXES THE LEVELLING FEET TO THE CHASSIS.
Attach the stabilising brackets as follows.
GXT6000 models:
1.
Using a Phillips-head screwdriver, remove the screws(4) from each of the
bottom corners of the side panels.
2.
Attach the stabilising brackets to each corner using screws just removed.
GXT10000 models :
1.
Using a Phillips-head screwdriver, remove the three inner-most screws at
the base of both side panels.
2.
Attach the stabilisers fixing with the screws just removed.
10 kVA
Levelling Feet Adjustment Diagram
6 kVA
12 mm
20