Liebert GXTTM User Manual page 15

6 & 10 kva 230v
Table of Contents

Advertisement

PROBLEM
Fault and Bypass
indicators and all load
level LED's are
illuminated
Fault and Bypass
indicators and
diagnostic LED A are
illuminated
Fault and Bypass
indicators and
diagnostic LED B are
illuminated
Fault and Bypass
indicators and
diagnostic LED D are
illuminated
Fault and Bypass
indicators and
diagnostic LED E are
illuminated
Fault indicators and
diagnostic LED A & C
are illuminated
Fault indicators and
diagnostic LED C & E
are illuminated
TROUBLESHOOTING GUIDE
CAUSE
UPS overloaded or load
equipment is faulty
UPS internal fan has a
problem or UPS
shutdown due to
temperature condition.
Load is on bypass
power.
UPS internal DC bus
over voltage
UPS PFC fault.
UPS inverter fault.
UPS failed the battery
test.
UPS shutdown due to a
command from the
communications port(s)
Check load level display and
remove non-essential loads.
Recalculate load VA and
reduce number of loads
connected to UPS. Check load
equipment for faults.
Press Alarm silence button.
Once the temperature is
reduced, the UPS will restart
and transfer the connected
equipment to inverter power
automatically.
UPS requires service. Contact
your dealer or technical
support.
UPS requires service. Contact
your dealer or technical
support.
UPS requires service. Contact
your dealer or technical
support.
Replace batteries. Contact
your dealer or technical
support.
Your UPS has received a
signal or command from the
attached computer. If this was
inadvertent, ensure the
communication cable used is
correct for your system. For
assistance, contact your dealer
or technical support.
13
SOLUTION

Advertisement

Table of Contents
loading

This manual is also suitable for:

Upstation gxt6000t-230xUpstation gxt10000t-230x

Table of Contents