Electrical Specifications - Liebert 610 Series Operation & Maintenance Manual

100-1000kva, 60hz three phase single-module
Hide thumbs Also See for 610 Series:
Table of Contents

Advertisement

5.5

Electrical Specifications

RECTIFIER INPUT
Input Voltage
Voltage Range
Frequency Range
Subcycle Magnetization Inrush
Input Current Walk-In
Current Limit
Current Distortion
Power Factor
BYPASS INPUT
Input Voltage
Voltage Range
Frequency Range
Voltage Transient
CRITICAL LOAD OUTPUT
Output Voltage
Voltage Regulation
Voltage Adjustment Range
Line Drop Compensation Range
Frequency
Slew Rate
Phase Balancing
Voltage Imbalance
20% Unbalanced Load
50% Unbalanced Load
Voltage Transient
20% Load Step
50% Load Step
100% Load Step
Loss or Return of AC Input Power
Manual Transfer of 100% Load
Voltage Transient Recovery Time
Voltage Harmonic Content
Overload at Full Output Voltage
Fault Clearing
Standard voltages for 100 - 450kVA units: 208, 480 and 600VAC
Standard voltages for 500 - 1000kVA units: 480 and 600VAC
Other voltages available on request. 3-phase, 3-wire plus ground.
+10%, -15% (no battery discharge at -20%)
57 Hz to 63 Hz
Less than 3 times normal full load input current for UPS models without optional
input isolation transformer. Typically less than 8 times normal full load input current
for models with optional input isolation transformer and optional input filter.
From 20% to 100% in 15-20 seconds
Maximum of 125% normal full load input current
Less than 30% reflected THD typical at normal full load input current. Less than 7%
reflected THD typical at normal full load input current with optional input filter.
For models with optional 12-pulse rectifier, less than 9% reflected THD typical at
normal full load input current. Less than 4% reflected THD typical with optional input
filter.
0.85 minimum lagging at full load
0.92 minimum lagging at full load with optional input filter
Standard voltages - 208/120 VAC, 480/277 VAC, 600/346 VAC. 3-phase, 3-wire
plus ground or 3-phase, 4-wire plus ground. Other optional voltages available.
Optional voltages - 208 VAC, 480 VAC, 600 VAC. 3-phase, 3-wire plus ground
(ungrounded or corner grounded delta). Other optional voltages available.
±5% for manually initiated bypass transfer
±10% for automatically initiated uninterrupted transfer
59.5 Hz to 60.5 Hz
±4% for manually initiated bypass transfer
Standard voltages - 208/120 VAC, 480/277 VAC and 600/347 VAC. 3-phase, 3-wire
plus ground or 3-phase, 4-wire plus ground. Other optional voltages available.
Optional voltages - 208 VAC, 480 VAC, 600 VAC. 3-phase, 3-wire plus ground
(ungrounded or corner grounded delta). Other optional voltages available.
±0.5% for balanced load
±2% for unbalanced load
±5% manually (front panel knob)
Up to +5% automatic load dependent
59.5 Hz to 60.5 Hz
0.01 to 1 Hz per second adjustable
120° ±1° for balanced loads
120° ±3° for 50% unbalanced loads
±1% from the arithmetic average of the 3 phases
±2% from the arithmetic average of the 3 phases
±4% RMS
±4% RMS for 100-750kVA units; ±5% RMS for 1000kVA units
±5% RMS for 100-750kVA units; ±8% RMS for 1000kVA units
±1% RMS
±4% RMS
To within 1% of steady state output voltage within 50 milliseconds
Maximum 5% RMS total, for any combination of linear and nonlinear 3-phase loads
Maximum 3% RMS single, for linear loads
104% of full load rating continuously
125% of full load rating for 10 minutes
150% of full load rating for 30 seconds
(with ±2% voltage regulation)
Up to 300% of normal full load current subcycle; up to 500% of normal full load
current for up to 40 milliseconds with bypass available; up to 1000% of normal full
load current for up to 16 milliseconds with bypass available.
96
Specifications