8.4 Electrical Characteristics (Input Rectifier)

Item
1
Rated AC input voltage
2
Input voltage range
2
Frequency
Power factor
Input power
Input current
Harmonic current distortion
Duration of progressive power
walk-in
Note:
1. Rectifiers operate at any of the rated supply voltages and frequencies without further adjustment.
2. At 305 V mains input, the UPS maintains the specified output voltage at rated load without discharging a previously charged battery.
3. IEC62040-3/EN50091-3: At rated load and input voltage 400 V, battery charged.
4. IEC62040-3/EN50091-3: At rated load and input voltage 400 V, battery charging at maximum rated power

8.5 Electrical Characteristics (Intermediate DC Circuit)

Item
Battery bus voltage
Quantity of lead-acid blocks
Float voltage
Temperature compensation
Temperature compensation
central point
Ripple voltage
Ripple current
Boost voltage
Boost control
EOD voltage
Battery charging power
and max charging current
2
(adjustable)
Note:
1. At low input voltage the UPS recharge capability increases as the load decreases (up to the maximum capacity indicated).
2. Max currents listed are for EOD voltage of 1.67 V/cell for 240 cells
58
Table 8-4 Rectifier AC Input (Mains)
Unit
Vac
Vac
Hz
kW / kVA, full load (half load)
3
kVA rated
(maximum
3
A rated
(maximum
THDI% FL
sec
Unit
Vdc
Nominal
Maximum
Minimum
V/cell (VRLA)
mV/°C/cl
°C
% V float
% C
10
V/cell (VRLA)
V/cell (VRLA)
1
kW
A
30
380/400/415 (3-phase and sharing neutral with the bypass input)
50/60 (tolerance: 40 Hz to 70 Hz)
4
)
32 (36)
4
)
46 (53)
5 sec to reach full rated current
(selectable 1 sec through 5 sec in 1-second intervals)
Table 8-5 Battery
Rated power (kVA)
30
Nominal: 384 (VRLA float charge is 436 V); range: 300 to 576
32 = [1 block (12 V)]
40 = [1 block (12 V)]
30 = [1 block (12 V)]
2.27 (selectable between 2.2 V/cell and 2.3 V/cell)
Constant current and constant voltage charge mode
3 (selectable between 0 and 5 mV/°C/cell , or inhibit)
25 (selectable between 20 and 30°C)
2.35 (selectable between 2.3 V/cell and 2.4 V/cell)
Constant current and constant voltage charge mode
Programmable automatic trigger or inhibit of boost mode
Float-boost current trigger 0.050 C
Boost-float current trigger 0.010 C
24 h safety time timeout (selectable between 8 h and 30 h)
Boost mode inhibit also selectable
Lower limit: 1.63 (selectable between 1.60 V/cell and 1.67 V/cell)
Upper limit: 1.75 (selectable between 1.67 V/cell and 1.85 V/cell)
4.5
11
User Manual 10H52192UM60 - Rev. 1 - 09/2011
Product Specifications
Rated power (kVA)
40
228 to 477
0.99 (0.98)
42 (51)
61 (75)
5
40
≤ 1
≤ 5
(selectable between 0.001 and 0.070)
10
(selectable between 0.001 and 0.025)
10
6 (9)
14.7 (22)
60
63.5 (72.5)
92 (106)
60
9
22

Advertisement