Liebert UPStation GXT User Manual

Liebert user manual 6kva maintenance bypass upstation gxt
Hide thumbs Also See for UPStation GXT:

Advertisement

P
P
OWER
ROTECTION
UPStation GXT
6kVA Maintenance Bypass
U
M
SER
ANUAL
Transformerless
with Configurable
Output Distribution

Advertisement

Table of Contents
loading

Summary of Contents for Liebert UPStation GXT

  • Page 1 OWER ROTECTION ™ UPStation GXT 6kVA Maintenance Bypass ANUAL Transformerless with Configurable Output Distribution...
  • Page 3: Table Of Contents

    TABLE OF CONTENTS MPORTANT AFETY NSTRUCTIONS ..........2 LOSSARY OF YMBOLS .
  • Page 5: Important Safety Instructions

    THIS MANUAL. FAILURE TO DO SO MAY RESULT IN SERIOUS INJURY OR DEATH. NEVER WORK ALONE. The UPStation GXT 6 kVA Maintenance Bypass is designed for use on properly grounded (earthed) 208/240VAC 60Hz supply, for installation by qualified personnel. This UPS equipment is...
  • Page 6: Glossary Of Symbols

    GLOSSARY OF SYMBOLS Risk of electrical shock Indicates Warning or Caution followed by important instructions Requests the user to consult the manual Equipment grounding conductor...
  • Page 7: General Description

    YSTEM ESCRIPTION The Liebert UPStation GXT 6 kVA Maintenance Bypass is intended for use with the UPStation GXT 6 kVA UPS. Typical applications include supporting workstations, servers, network, telecom or other sensitive electronic equipment.
  • Page 8 Maintenance Bypass component layout Bypass availability UPS input power indicator (amber) present (amber) UPS input switch (SW2) Output breaker (CB1) Configurable Output Distribution TOP VIEW Bypass switch (SW1) UPS output availability indicator (green) GND3 GND1 1 2 2 GND2 Utility input input INSIDE VIEW—...
  • Page 9: Major Components

    MAJOR COMPONENTS The following is a general description of each component and its functions. Please review this section carefully, as it will give you a better understanding as to how the UPStation GXT 6 kVA Maintenance Bypass operates. YPASS WITCH...
  • Page 10: Cable Installation

    CABLE INSTALLATION IRING REPARATION CAUTION Please read this section thoroughly before attempting to install wiring to this unit. Be sure that the unit is not connected to any AC mains power source or UPS before installing any wiring to this unit. This should be installed by a qualified/certified electrician.
  • Page 11 Connecting Maintenance Bypass to UPStation GXT6000T - 208 GND3 Utility GND2 Utility input NOTE GMB12 models are supplied with an attached input power cord complete with L14-30 plug. Output MAINTENANCE BYPASS GND1 UPS input UPS output Input Output GXT6000T - 208 NOTE When using the Maintenance Bypass with an UPStation...
  • Page 12 Connecting Maintenance Bypass to UPStation GXT6000T - 208X GND3 Utility GND2 Utility input NOTE GMB12 models are supplied with an attached input power cord complete with L14-30 plug. 120V 208V 120V Output TB4 MAINTENANCE BYPASS GND1 UPS input UPSoutput Input GXT6000T - 208X Output Ext.
  • Page 13 Connecting Maintenance Bypass to UPStation GXT6000T - 240X GND3 GND2 Utility input NOTE GMB12 models are supplied with an attached input power cord complete with L14-30 plug. 120V 240V 120V Output TB4 MAINTENANCE BYPASS GND1 Utility UPS input UPSoutput Input GXT6000T - 240X Output Ext.
  • Page 14: Wall-Mount Diagram

    Use the following diagram, which shows the location and measurements of factory-cut mounting slots, when preparing to attach the GXT Maintenance Bypass to a wall. Liebert recommends using 1/4-20 mounting screws. Rubber pads are supplied for placing the Maintenance Bypass on the floor.
  • Page 15: Hardwire Output Option

    HARDWIRE OUTPUT OPTION This product is intended to be installed by a qualified electrician only. 1. COMPLETELY REMOVE ALL POWER FROM THE FRAME. If the Maintenance Bypass is connected to the UPS, disconnect external battery supply. 2. Remove the end cover plate to access the terminal block (see Accessing terminal block below).
  • Page 16: Operating Procedures

    OPERATING PROCEDURES START-UP AND INITIALIZATION Follow these steps in order to start up the GXT 6kVA UPS while connected to the Maintenance Bypass. AINTENANCE YPASS 1. Set the Maintenance Bypass switch (SW1) to UPS position. 2. Close (position I) UPS Input switch (SW2). 3.
  • Page 17: Specifications

    SPECIFICATIONS Typical Transfer Time (to or from maintenance bypass) Input Voltage Total Current Operating Ambient Temperature Storage Ambient Temperature Dimensions, W x D x H, in (mm) Chassis Weight (no receptacles) Distribution Module Weights (each) Connections to UPS Humidity Agency/Standards <...
  • Page 20 UPStation GXT 6kVA Maintenance Bypass The Company Behind the Products With over a million installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics: •...