OWER VAILABILITY ™ Series 600T NSTALLATION ANUAL Single Module Three-Phase 65-225 kVA 60 Hz...
Page 2
FACTURER PRIOR TO MOVING A BATTERY CABINET. Battery cabinets contain non-spillable batteries. Keep units upright. Do not stack. Do not tilt. Failure to heed this warning could result in smoke, fire or electric hazard. Call 1-800-LIEBERT prior to moving battery cabinets.
WIRING INSPECTION ............21 WARNING LOCATE CENTER OF GRAVITY SYMBOLS AND DETERMINE UNIT WEIGHT BEFORE HANDLING CABINET If you require assistance for any reason, call the toll-free Liebert Global Services number, 1-800-543-2378. Please have the following information available: Part Number: ________________________________________________________...
Page 4
Table 1. Power Wiring Terminals - Factory Supplied ...22 Table 2. Torque Specifications ...22 Table 3. Field-Supplied Lugs ...23 Table 310-16, NEC Allowable Ampacities of Insulated Conductors...24 Figure 1. Preferred Grounding Configuration, 480 or 600 VAC input and output ....8 Figure 2.
Carefully read the text below each Danger, Warning, Caution, and Note and use professional skills and prudent care Liebert Series 600T UPS, 65-225 kVA, Single Module when performing the actions described by that text. A Danger signals immediate hazards resulting in severe personal injury or death.
(consult your Liebert sales representative). 7. Even though your Liebert UPS unit is 92.5 to 94% efficient, the heat output is substantial. For more specific information, see the Site Planning Data (Appendix A).
ELECTRICAL HAZARD. CALL 1-800- LIEBERT PRIOR TO RELOCATING BATTERY CABINET (AFTER INITIAL INSTALLATION). Liebert Series 600T UPS, 65-225 kVA, Single Module 4. INSPECTIONS 4.1. External Inspections 1. While the UPS system is still on the truck, inspect the equipment and shipping container(s) for any signs of damage or mishandling.
5. EQUIPMENT LOCATION 1. Handle cabinet(s) in accordance with WARN- INGS in Section 3. Use a suitable material handling device to move each cabinet to its final location. Exercise extreme care because of the uneven weight distribu- tion. Carefully lower the cabinets to the floor and position them for reconnection, if applica- ble.
Page 11
2. Utiliser des outils avec manchon isolé. 3. Porter des gants set des bottes decautchouc. Liebert Series 600T UPS, 65-225 kVA, Single Module 4. Ne pas déposer les outils ou les pièces métalliques sur le dessus des accumulateurs. 5. Interrompre la source de charge avant de raccorder ou de débrancher les bornes de la...
Exercise caution; voltage is present within the Battery Cabinet even before installation. If there are signs of damage, do not proceed. Call Liebert Global Services at 1- 800-542-2378. 3. Battery Storage. The batteries used in the Battery Cabinet retain their charge well. The batteries can be stored for up to six months without any appreciable deterioration.
(i.e. positive-with-positive and negative-with-negative) can cause stress or damage to the cables, conduit or buswork. Liebert Series 600T UPS, 65-225 kVA, Single Module 7. CONFIGURING YOUR NEUTRAL AND GROUND CONNECTIONS Improper grounding is the largest single cause of UPS installation and start-up problems.
Isolated Power Distribution Units, Wye-Connected Service One of the most-common configurations of the Series 600T UPS is the Single Module System with 480 VAC input, 480 VAC output, and a connected load consisting of multiple Power Distribution Units (PDUs) with isolation transformers in the PDUs to produce 208 VAC.
(GFIs) and distorting the bypass waveform reference. Proper adjustment of ground fault interrupters is necessary to avoid unwanted tripping. Liebert Series 600T UPS, 65-225 kVA, Single Module This configuration is reserved for those applications which meet all the following criteria: •...
GROUNDING ELECTRODE PER NEC 250-24 Figure 3. Preferred Grounding Configuration, 480 or 600 VAC input and 208 VAC output 7.3. Preferred Grounding Configuration, 480 or 600 VAC Input, 208VAC Output, and Isolated Bypass Another configuration in this power range is the Single Module System with 480 or 600 VAC input, 208 VAC output, a Bypass Isolation Transformer and a connected load consisting of multiple...
In this configuration, the UPS module is not considered a separately derived source. Liebert Series 600T UPS, 65-225 kVA, Single Module The UPS module output neutral and the load neutral are solidly connected to the building service neutral, which is bonded to the grounding conductor at the service entrance equipment.
UPS ground. See Figure 5 above. If the building service is corner-grounded delta or an impedance-grounded wye, the UPS requires the Series 600T Isolated Neutral Kit. This kit uses control isolation transformers to create a reference point. For this application, the UPS output neutral must not be bonded to the UPS ground.
Power-Tie equipment also permit the operator to continuously parallel the output of the UPS modules. Liebert Series 600T UPS, 65-225 kVA, Single Module In tied systems, each UPS module must have its neutral solidly connected to its own building service neutral and to the Power-Tie switchgear neutral.
GROUNDING ELECTRODE PER NEC 250-24 Figure 7. Preferred Battery Cabinet Grounding Configuration 7.7. Preferred Grounding Configuration, Battery Systems Large, open-rack battery systems are normally either locally grounded or left ungrounded, depending on local code requirements. Battery cabinet systems, on the other hand, should be grounded to the UPS ground bus bar.
Standard SMS, with 208/208, 480/480 or 600/600 Standard SMS, with 208/208, 480/480 or 600/600 VAC input/output. VAC input/output. Bypass Isolation Xfmr Bypass Isolation Xfmr Figure 8. Typical One-Line Diagrams for SMS with Standard Dual Input SMS with input isolation transformer and 208/208, SMS with input isolation transformer and 208/208, 480/480 or 600/600 VAC input/output.
Figure 9. Typical One-Line Diagrams of SMS with optional single input. Liebert Series 600T UPS, 65-225 kVA, Single Module Single-input SMS with input isolation transformer and 208/208, 480/480 or 600/600 VAC input/output.
2-breaker Maintenance Bypass Cabinets for standard (left) and single-input (right) modules. 3-breaker Maintenance Bypass Cabinets for standard (left) and single-input (right) modules. BYPASS ISO XFMR (OPT.) 3-breaker and 4-breaker Maintenance Bypass Cabinets for stepdown-voltage applications. Figure 10. Typical One-Line Diagrams of SMS with optional Maintenance Bypass Cabinets Abbreviations for Circuit Breakers Bypass Isolation Breaker Maintenance Bypass Breaker...
NEC standards. However, NEC Class 1 wiring methods are required for these circuits to ensure proper operation of the UPS. Liebert Series 600T UPS, 65-225 kVA, Single Module 8.3. Battery Wiring Power wiring to the Battery Cabinet connects positive, negative, and ground power cables from the Battery Cabinet to the associated UPS.
9.2 Specific Connections Refer to the drawings in this manual and any other drawings provided by Liebert for this installation. Make all of the following connections: a. AC power cables from input power source circuit breaker to UPS Module Input. Observe phase rotation.
Power and control connections required for the Maintenance Bypass. Any additional special wiring required at the customer site. Liebert Series 600T UPS, 65-225 kVA, Single Module 10. WIRING INSPECTION 1. Verify all power connections are tightened per the torque specifications in Table 2. Verify all control wire terminations are tight.
Power Wiring Terminals - Factory Supplied MODULE Bypass input wiring is top-entry, to busbars on top of the circuit breaker. Rectifier 65 & 80 kVA input wiring is top-entry, directly to lugs on top of the input circuit breaker. DC link and critical bus output connections are top entry, to frame-mounted lugs.
Table 310-16. Allowable Ampacities of Insulated Conductors Not More Than Three Conductors in Raceway or Cable or Earth (Directly Buried), Based on Ambient Temperature of 30 (86F) Size 75°C (167°F) (140°F) TYPES TYPES FEPW=, RH, RHW=, THHW=, kcmil THW=, THWN=, XHHW=, USE=, ZW= COPPER...
Figure 58. Circuit Breaker Schedule, Maintenance Bypass Cabinet, 65 through 225 kVA Installation Manual...
Page 79
12. Control wiring and power cables must be run in separate conduits. Control wiring must be stranded tinned conductors. 13. 7% maximum reflected input harmonic current and 0.92 lagging input power factor at full load with optional input filter. Liebert Series 600T UPS, 65-225 kVA, Single Module Appendix A: Site Planning Data...
Page 80
Series 600T Single Module Systems Output UPS Rating Voltage Options Input Input Filter Xformer Applicable Notes: 208 Volt Input Inverter Or Required Bypass AC Battery Rectifier AC Output Discon- Input Current Current nect Rating Amperes 1,4,8, 2,3,5,7,8, 9,11,12 9,11,12 Maximum...
Page 81
Output UPS Rating Voltage Options Input Input Filter Xformer Applicable Notes: Liebert Series 600T UPS, 65-225 kVA, Single Module Series 600T Single Module Systems 480 Volt Input Inverter Or Required Maximum Rectifier Bypass AC Battery AC Input Output Discon- Current At...
Page 82
Rectifier AC Output UPS Rating Voltage Options Input Input Filter Xformer Applicable Notes: Series 600T Single Module Systems 600 Volt Input Inverter Or Required Maximum Bypass AC Battery Battery Input Output Discon- Current At Current Current nect End Of Rating...
Page 83
Liebert Series 600T UPS, 65-225 kVA, Single Module...
Series 600T The Company Behind the Products With over a million installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics: •...